Potterton Solar - Solar Thermal Domestic Hot Water System

20

3.2.5 Frost protection

This function can be switched on/off in the “Basic settings”

menu, point 11 and the start temperature can be adjusted

in point 13. Furthermore, a frost protection sensor can be

selected (T1-T6, point 12).

For systems driven without or with very low amounts of

antifreeze, the pipes and the collector have to be protected

from freezing. For this purpose, the selected frost

protection sensor measures the temperature at an exposed

place, e.g. blank pipes before the collector. If the measured

value is lower than the start temperature, the solar pump

is activated until the adjusted frost protection start

temperature +5K is reached.The minimum runtime of

the pump is 5 minutes.

For security reasons the function is deactivated if the

temperature of the priority storage falls below 5ºC.

3.2.6 Energy productivity measurement

For the purposes of energy productivity measurement

(solar gain), a sensor on the collector return line and a

flow meter are required.The yield value is calculated

from the values of the temperature difference between

the collector and collector return line and the value

measured by the flow meter. This function is switched on

and off in the “Basic settings” menu.

3.2.7 Operating hours meter

So long as the storage tank is charged by a pump, the

operating hours meter records for each separate pump.

The number of operating hours can be read in menu

“info” and for each pump separately reset to 0.