Potterton Solar - Solar Thermal Domestic Hot Water System

19

3.2.2 Flow monitoring

If the energy productivity measurement option is

deactivated, the temperature difference between

collector and storage tank is checked.

If it exceeds the amount of (60K + dTmax), it is then

interpreted as an error because in the case of normal

system dimensioning and a pump switched on such large

differences cannot take place.

If the energy productivity measurement option is

activated, the flow amount when the pump is switched

on is checked. If for 15 minutes no flow is recognised

it is evaluated as an error.

Error message is automatically reset after eliminating

the failure.

3.2.3 Collector protection / Re-cooling

This function can be switched on/off in the “Basic settings”

menu.

High temperatures can destroy antifreeze liquids.Therefore,

the maximum collector temperature should be restricted.

When all storages have been loaded to the limit, the solar

pump is switched off. If the collector temperature rises

above “T collector max”, the solar pump is switched on,

until the collector temperature drops by 10K. Part of the

energy is lost in the pipes, the rest is loaded in the storage,

which results in increasing the storage temperature above

the adjusted maximum storage temperature. For security

reasons the function will be interrupted if the storage

reaches 95ºC.

If the storage temperature is bigger TStmax+2K and the

collector temperature is 10K below TSt, then the re-cooling

function is activated.The redundant storage energy will be

released through the collector in order to assure reserves

for the next loading cycle.

The re-cooling ends when TSt drops below the value “re-

cooling till…” in the “Basic settings” menu, point 3, or

when the collector temperature >= the storage

temperature – 2K.

The re-cooling function can be active only when the

collector protection function is on.

3.2.4 System protection function

The system protection function switches the system off if

the “maximum collector temperature” is exceeded by 10K.

As soon as the temperature drops below the “maximum

collector temperature”, the system is started up again.This

function has higher priority and is always active, regardless

of whether the collector protection is on or off.

“Basic SETTINGS”

“Programming”

0 -- 1

---

1 -- 120ºC

2 -- 1

3 -- 40ºC

Corresponding values in menu

Indication

Meaning

+

Missing circulation in solar circuit

!