Potterton Solar - Solar Thermal Domestic Hot Water System

13

3.0

Commissioning of solar controller

3.1.6 Menu “Programming”

All adjustable parameters can be checked in this menu

and, if necessary, changed.The default factory set values

will usually give efficient, problem free operation.

The number of indicated values depends on the

controller type and the adjusted additional functions.

Only the required values are shown at each menu step:

Indication

Description

Value range

Defaults

max

Storage 1/2:

15..95ºC

65ºC

65ºC

Maximum temperature

dT max

Storage 1/2: Hysteresis (Tdon)

3..40 K

7 K

7 K

dT min

Storage 1/2: Hysteresis (Tdoff)

2..35 K

3 K

3 K

min

Setting the speed control of the pump

30%..100%

100%

100

100% = speed control off

13:21

Clock

0:00...23.59

12:00

min

Temperature start for the function

20..90ºC

40ºC

40ºC

heating/cooling

dT

Hysteresis heating/cooling

1..30K

10K

10K

max

Differential controller: Maximum

15..95ºC

65ºC

65ºC

temperature of heat target Tmax

min

Differential controller: Maximum

0..95ºC

15ºC

15ºC

temperature of heat source Tmin

dTmax

Temperature differential controller:

3..40K

7K

7 K

Hysteresis dTmax

dT min

Temperature differential controller:

2..35K

3K

3 K

Hysteresis dTmin

min

Timeframe 1(2,3): Start

0:00...

00:00

00:00

for the independent controller

23.59

1(2,3)

max

Timeframe 1(2,3): Stop

0:00...

23:59

23:59

for the independent controller

23:59

1(2,3)

min

Timeframe 1(2,3): Start

0:00...

6:00

6:00

for the tube collector function

23:59

4

max

Timeframe 1(2,3): Stop

0:00...

20:00

20:00

for the tube collector function

23:59

4

2