Set iochannel analog (temperature) – Perle Systems 5500208-41 User Manual
Page 86
Set IOChannel
86
IOLAN DS1/TS2 CLI Reference Guide, Version 4.1
Set IOChannel Analog (Temperature)
Description Sets the Analog input channel settings for Temperature models.
User Level Admin
Syntax
set iochannel <analog_channel> type rtd|thermocouple
range <range_specifier>
set iochannel <analog_channel> alarm
[level 1|2|3|4|5 [mode on|off] [trigger-type disabled|low|high]
[trigger-level <decimal_value>] [clear-mode auto|manual]
[clear-level <decimal_value>] [snmp on|off] [syslog on|off]]
Options
analog_channel
Specify the Analog channel number, for example, a2 or a4 (this also applies to
Temperature models).
type
Specify the type of sensor you are using to measure temperature, either RTD or
thermocouple. The default is RTD.
range
Specify the temperature range that you want to measure. For RTD, the range is:
z
1 (Pt100 a=385 -50 to 150C) This is the default.
z
2 (Pt100 a=385 0 to 100C)
z
3 (Pt100 a=385 0 to 200C)
z
4 (Pt100 a=385 0 to 400C)
z
5 (Pt100 a=385 -200 to 200C)
z
6 (Pt100 a=392 -50 to 150C)
z
7 (Pt100 a=392 0 to 100C)
z
8 (Pt100 a=392 0 to 200C)
z
9 (Pt100 a=392 0 to 400C)
z
10 (Pt100 a=392 -200 to 200C)
z
11 (Pt1000 a=385 -40 to 160C)
z
12 (NiFe604 a=518 -80 to 100C)
z
13 (NiFe604 a=518 0 to 100C)
For thermocouple, the range is:
z
b (B 500 to 1800C)
z
e (E 0 to 1000C)
z
j (J 0 to 760C) This is the default.
z
k (K 0 to 1370C)
z
r (R 500 to 1750C)
z
s (S 500 to 1750C)
z
t (T -100 to 400C).
alarm
Configures alarm settings when the Analog input trigger is activated.