HID-DynaVision Control SON

Electrical installation notes

Mains operation
Rated mains voltage

220 - 240 V

With tolerances for performance

203 - 254 V

With tolerances for operation

180 - 264 V

Mains frequency

50/60 Hz

Operation frequency (typical)

50 Hz

Power factor* (nominal power)

> 0.92

Power factor* (35% power)

> 0.7

* With rated PF capacitor value
Earth leakage current (per gear)

< 0.5 mA

Overvoltage protection

48 hrs at 325 Vac
2 hrs at 366 Vac
5 min at 400 Vac

Cable length to normal gear

No limit.

Notes:
1. With three-phase mains supply, neutral should never be
disconnected; otherwise circuitry could be damaged.
2. Gear must be earthed.
3. Power factor correction capacitor should be connected directly
on the mains; when installing this device in front of existing gear, the
original capacitor has to be removed.

Control characteristics

Control input
Control voltage input

1-10 V

Protected against mains voltage
connection

Yes

Control resistance (to be
connected on 1-10V input)

0 - 100 kΩ

Regulating light level SON
250/400 W

20 - 100%

After ignition or lamp restrike allways 100% level for 5 min
Gear dimming fading rates are:
SON 250/400 W
Fade up (35-100%)

< 1.0 min

Fade down (100-35%)

< 1.5 min

Mechanical installation notes

Wire cross-section:
On the mains side

0.75…2.5 mm

2

On the lamp side

0.75…2.5 mm

2

Strip length

6 mm