Hid-dynavision son and cdo, Inrush current, Electrical data – Philips 220-230-240V User Manual
Page 109: Ordering and packing data

OEM Catalogue 2009/2010
3.109
HID Gear
D1
A2
B1
B2
A3
A1
C1
HID-DV
Type
A1Nom
A2Nom
A3Nom
B1Nom
B2Nom
C1Nom
D1Nom
HID-DynaVision 1-10V SON/CDO
150.0
134.0
136.0
90.0
70.0
40.0
4.5
HID-DynaVision SON and CDO
Inrush current
Type
Maximum
gear number
on MCB
(x)
Inrush
current
Peak
(A)
Inrush
current
Width
(ms)
HID-D 1-10V 100/150 SON/CDO
8
50
0.5
HID-D 1-10V 70 SON/CDO
12
35
0.5
Electrical data
Type
Number
of
Lamps
(x)
Rated
Gear-
Lamp
Power
Line
Frequency
(Hz)
Line
Voltage
(V)
T-case
life
(ºC)
T-case
maximum
(ºC)
T-ambient
Ignition
Voltage
(kV)
Cable-Cap
outputwires
mutual
(pF)
HID-D 1-10V 100 /S CDO 220-240V
1
100
50/60
220-240
90
100
50
4.00
200
HID-D 1-10V 100 /S SON 220-240V
1
100
50/60
220-240
90
100
50
4.00
1000
HID-D 1-10V 150 /S CDO 220-240V
1
150
50/60
220-240
90
100
45
4.00
200
HID-D 1-10V 150 /S SON 220-240V
1
150
50/60
220-240
90
100
45
4.00
1000
HID-D 1-10V 70 /S CDO 220-240V
1
70
50/60
220-240
90
100
50
2.50
200
HID-D 1-10V 70 /S SON 220-240V
1
70
50/60
220-240
90
100
50
2.50
1000
Ordering and packing data
Type
Weight
Qty bulk
packing
Dimensions bulk packing
EAN code
bulk packing
EOC
8711500
HID-D 1-10V 100 /S CDO 220-240V 50/60Hz
0.725 kg
10
39.8 cm x 16 cm x 11.1 cm
8711500931337
931320 30
HID-D 1-10V 100 /S SON 220-240V 50/60Hz
0.725 kg
10
39.8 cm x 16 cm x 11.1 cm
8711500749062
749055 30
HID-D 1-10V 150 /S CDO 220-240V 50/60Hz
0.725 kg
10
39.8 cm x 16 cm x 11.1 cm
8711500538109
538093 30
HID-D 1-10V 150 /S SON 220-240V 50/60Hz
0.725 kg
10
39.8 cm x 16 cm x 11.1 cm
8711500538086
538079 30
HID-D 1-10V 70 /S CDO 220-240V 50/60Hz
0.725 kg
10
39.8 cm x 16 cm x 11.1 cm
8711500931351
931344 30
HID-D 1-10V 70 /S SON 220-240V 50/60Hz
0.725 kg
10
39.8 cm x 16 cm x 11.1 cm
8711500927330
927323 30
Electrical installation notes
Mains operation
Rated mains voltage
220 - 240 V
With tolerances for performance
+6%-8%
203 - 254 V
With tolerances for operation
180 - 264 V
Mains frequency
50/60 Hz
Power factor 100% power
> 0.98
Power factor 35%, SON, 60%,
CDO, power
> 0.93
Earth leakage current
< 0,5 mA per driver
Overvoltage protection
48 hrs at 325 Vac
2 hrs at 366 Vac
5 min. at 400 Vac
Lamp operation
Operation frequency (typical)
125 Hz
Ignition voltage
3 - 4 kV
Cable capacity
SON
Max. 1 nF
CDO
Max. 200 pF
Air and creepage distance from any
(metal) part that may become live,
to earthed environment (class I) or
test finger (class II)
> 4 mm