3.3.6 Emergency Module Off
The Local Emergency Module Off (LEMO) mode is used to remove power from nearly all UPS module
components, and the critical load will continue to be supplied through the bypass line.
The Emergency Module Off control is a guarded pad on the UPS Control Panel (Figure 4).
Lift the cover and press the pad. The load will be transferred to bypass, and the battery (MBD), input
and output circuit breakers will be opened (tripped). This will remove power from all UPS module
components except the controls, bypass circuit breaker and the static switch.
Refer to 3.4.4 - Shutdown Procedures.
Figure 47 Emergency modules off
Controls
Bypass CB
Static
Bypass
Switch
RIB
BFB
Critical
Load
AC Output
Static
Switch
Disconnects
THREE BREAKER MAINTENANCE BYPASS SWITCHBOARD
CONTROL POWER
UPS MODULE
MAIN INPUT
SWITCHGEAR
OUTPUT
CB
Rectifier/
Charger
INPUT
CB
Inverter
Battery
MBD
BIB
MBB
MIB
- PS250-50S (12 pages)
- SGH STEAM SL-14050 (16 pages)
- Ship-Ahead Input/Output Cabinet NXL (20 pages)
- NfinityTM (44 pages)
- 4000 (59 pages)
- 230V (40 pages)
- PSP (32 pages)
- UPStation GXT (20 pages)
- UPSTATION GXT 2U (38 pages)
- UPS Systems PSI XR (32 pages)
- 600TTM (91 pages)
- Series 600T (128 pages)
- GXT2 - 3X1 (42 pages)
- Nfinity (44 pages)
- PowerSure PSA 350VA to 1000VA (8 pages)
- 2U (16 pages)
- PDUTM (156 pages)
- GXT2-6000 RT208 (52 pages)
- PowerSure Personal (12 pages)
- 2700VA (40 pages)
- Series 610 (44 pages)
- Emerson NX UPS System (88 pages)
- GXT 2U (44 pages)
- UPStation S VM12000 (38 pages)
- 1000kVA (120 pages)
- Nfinity 208 V / 240 V 60Hz (45 pages)
- UPS (28 pages)
- UPS System (121 pages)
- PowerSure PSI 1000 - 3000VA 60 Hz 120V (36 pages)
- GXT2-4500RT230 (40 pages)
- GXT2-6000RTL630 (44 pages)
- IntelliRack (2 pages)
- PowerSure PSA 350-1000VA (2 pages)
- 350-700 VA (11 pages)
- 500-650 VA (24 pages)
- PowerSure PS250-60S (13 pages)
- 130 kVA (102 pages)
- 30-130kVA (112 pages)
- GXT (23 pages)
- PSITM (34 pages)
- 600T (73 pages)
- 600T (88 pages)
- GXTTM (30 pages)
- 700-3000 VA (30 pages)