Status/alarm message areas, Figure 8, Monitor/mimic display example: normal power flow – Liebert 610 User Manual
Page 30

Operation
24
Status/Alarm Message Areas
The status/alarm message areas display vital information about the operation of the UPS system.
During normal operation no alarm messages should be present. Changes in the status of the system
and possible alarm conditions can be monitored. Both the status and the alarm messages are dis-
played in reverse video (highlighted—light on dark). The alarm messages continue flashing until the
Horn Off pad is pressed. To clear a latching alarm, you must also press the Alarm Reset pad after
the alarm condition is corrected.
The following lists show the status and alarm messages that may be displayed in these areas. For
more information and the corrective actions for these messages, refer to Table 4 in this section.
Item 6 - Status Messages
Static Switch Connected
Static Switch Disconnected
OK To Transfer
Not OK To Transfer
Item 7 - Alarm Messages
Figures 8 through 11 illustrate how the Monitor/Mimic Display screens depict the power flow
through the UPS.
Figure 8
Monitor/Mimic display example: Normal power flow
Input Fail
Output Over/Underfrequency
DC Ground Fault
Output Undervoltage
DC Capacitor Fuse Blown
Output Overvoltage
Battery CB Open
Overload
Battery Discharging
Overload Transfer
Low Battery Warning
Inverter Non-Sync
Low Battery Shutdown
Reverse Power
DC Overvoltage Shutdown
Rectifier Fuse Blown
Load On Bypass
Inverter Fault
Auto Retransfer Primed
Hardware Shutdown
Manual Reset/Retransfer
Emergency Off
Static Switch Unable
Battery Cycle Buffer Warning
Bypass Not Available
Ambient Overtemperature
Bypass Phase Sequence Wrong
Blower Failed
Control Power Fail
Equipment Overtemperature
Battery Overtemp
Overtemperature Time-out
Battery Exercise
UPS INPUT PWR
480V 480V 480V
350A 350A 350A
BATTERY
VOLTS 540
AMPS 15 CHARG
UPS RATINGS
A-B B-C C-A
480V 480V 480V
60.0 Hz
AP658-64
RATED 500 KVA
OUTPUT VOLTAGE
BYPASS INPUT
A-B B-C C-A
480V 480V 480V
60.0 Hz
LOAD
A B C
270 KVA / 217 KW
325A 325A 325A
A-B B-C C-A
OK to Transfer
Static Switch Connected