Model Number
GXT2-2000RT230
GXT2-3000RT230 / 3KRT230E
Model Rating
2000VA / 1400W
3000VA / 2100W
DIMENSIONS: mm
Unit W x D x H: mm
87 x 547 x 430
87 x 618 x 430
Shipping W x D x H: mm
268 x 692 x 585
268 x 692 x 585
WEIGHT: kg
Unit: kg
24.7
31.9
Shipping: kg
28.7
35.9
INPUT AC PARAMETERS
Voltage Range
(typical)
230 VAC nominal;
variable based on output load
100% - 90% loading
176VAC / 280VAC
176VAC / 280VAC
90% -70% loading
159VAC / 280VAC
159VAC / 280VAC
70% -30% loading
139VAC / 280VAC
139VAC / 280VAC
30% - 0% loading
119VAC / 280VAC
119VAC / 280VAC
Frequency
40 - 70 Hz; Auto Sensing
Input Connector
IEC320-10A
IEC320-16A
OUTPUT AC PARAMETERS
Output Sockets
(4) IEC320-10A
(4) IEC320-10A,
(1) IEC320-16A
Voltage
200/208/220/230/240 (user configurable) VAC; ±3%
Frequency
50 Hz or 60 Hz
Waveform
Sinewave
Main Mode
Overload
200% for 8 cycles;
130% for 10 seconds with transfer to bypass
BATTERY PARAMETERS
Type
Valve-regulated, nonspillable, flame retardant, lead acid
Qty x V x Rating
4 x 12V x 9.0 AH
6 x 12V x 9.0 AH
Battery Mfg/Part #
Panasonic UP-VW1245P1
Yuasa / REW 45-12 FR
Back-up Time
Recharge Time
5 Hours to 95% capacity after full discharge
into 100% load (Internal Batteries Only)
ENVIRONMENTAL
Operating Temp
0°C to +40°C (+32°F to +104°F)
Storage Temp
-15°C to +50°C (+5°F to +122°F)
Relative Humidity
0% to 95%, non-condensing
Operating Elevation
Up to 3000 m (10,000 ft.) at 40°C (104°F) without derating
Storage Elevation
15,000 m (50,000 ft.) maximum
Audible Noise
<55 dBA, at 1 metre from the rear
<50 dBA, at 1 metre from the front or sides
AGENCY
Safety
EN50091-1-1, CE compliance mark,
for both Low Voltage and EMC Directives
RFI/EMI
EN 50091-2, Class B
Surge Immunity
EN 61000 4-2, 4-3, 4-4, 4-5
Transportation
ISTA Procedure 1A