beautypg.com

4 battery charger, 5 dc to dc converter, 6 battery – Liebert 230V User Manual

Page 10: 7 dynamic bypass, Battery charger, Dc to dc converter, Battery, Dynamic bypass

background image

Major Components

6

4.4

Battery Charger

The battery charger utilizes energy from the mains power and pre-

cisely regulates it to continuously “float charge” the batteries. The bat-

teries are being charged whenever the UPStation GXT 2U is plugged

in, even when the UPS is not turned on.

4.5

DC to DC Converter

The DC to DC converter utilizes energy from the battery system and

raises the DC voltage to the optimum operating voltage for the

inverter. This allows the inverter to operate continuously at its opti-

mum efficiency and voltage, thus increasing reliability.

4.6

Battery

The UPStation GXT 2U utilizes valve-regulated, nonspillable, flame

retardant, lead acid batteries. To maintain battery design life, operate

the UPS in an ambient temperature of 20°C to 25°C (68°F to 77°F).

Optional external battery cabinets are available to extend battery run

times.

4.7

Dynamic Bypass

The UPStation GXT 2U provides an alternate path for mains power to

the connected load in the unlikely event of a UPS malfunction. Should

the UPS have an overload, overtemperature, or UPS failure condition,

the UPS automatically transfers the connected load to bypass. Bypass

operation is indicated by an audible alarm and illuminated amber

Bypass LED (other LEDs may be illuminated to indicate the diag-

nosed problem). To manually transfer the connected load from the

inverter to bypass, press the Standby button once.

NOTE
The bypass power path does NOT protect the connected

equipment from disturbances on the mains supply.