2 standby/manual bypass button, 3 load/battery level indicators (4 green, 1 amber), 4 fault indicator led (red) – Liebert 230V User Manual

Page 19: 5 bypass indicator led (amber), 6 ups on indicator led (green), Standby/manual bypass button, Load/battery level indicators (4 green, 1 amber), Fault indicator led (red), Bypass indicator led (amber), Ups on indicator led (green)

background image

Controls and Indicators

15

6.2

Standby/Manual Bypass Button

This button controls output power to connected load(s) and has

dual functions: Standby and Manual Bypass.

6.3

Load/Battery Level Indicators (4 Green, 1 Amber)

The load/battery level indicators have dual functions. During normal

mode operation LED indicators display the approximate electrical

load placed upon the UPS; and during battery mode operation LED

indicators display approximate battery capacity.
The UPStation GXT 2U is equipped with automatic and remote bat-

tery test features. The automatic test occurs every 14 days (this option

is user configurable) if mains has not been interrupted. Should the

battery fail this test, the red Fault indicator LED along with the A and

C diagnostic LEDs will illuminate and an alarm will sound (refer to

11.0 - Troubleshooting). The remote test feature functions with

MultiLink 3 software and can remotely initiate the battery test.

6.4

Fault Indicator LED (Red)

The Fault indicator LED is illuminated if the UPS has detected a

problem. Also, one or more of the load/battery level indicators may be

illuminated (refer to 11.0 - Troubleshooting).

6.5

Bypass Indicator LED (Amber)

The Bypass indicator LED is illuminated when the UPS is operating

from bypass power. An alarm will sound indicating the UPS detected

a problem, or the manual bypass function has been activated.

6.6

UPS ON Indicator LED (Green)

The UPS ON indicator LED is illuminated when the UPS inverter is

operating and supplying power to your connected loads.

!

CAUTION

While the UPS is in Normal Mode operation, pressing the

Standby/ Manual Bypass button once will put the UPS into

Bypass Mode.
Once the UPS is in Bypass Mode operation, press the Standby/

Manual Bypass button two distinct times (for about one

second each time) to turn off the UPS. Perform all necessary

shutdown procedures on connected loads before turning off the

UPS.