Ratings

Notes:

1. The ratings are based on standard test procedures prescribed

by the United States Department of Energy.

2. Net AHRI ratings are based on net installed radiation of

suffi cient quantity for the requirements of the building
and nothing need be added for normal piping and pickup.
Ratings are based on a piping and pickup allowance of 1.15.

3. Knight XL boilers require special gas venting. Use only

the vent materials and methods specifi ed in the Knight XL
Installation and Operation Manual.

4. Standard Knight XL boilers are equipped to operate from

sea level to 4,500 feet only with no adjustments. The boiler
will de-rate by 4% for each 1,000 feet above sea level up to
4,500 feet.

5. High altitude Knight XL boilers are equipped to operate

from 3,000 to 12,000 feet only with no fi eld adjustments.
The boiler will de-rate by 2% for each 1,000 feet above
3,000 feet. High altitude models are manufactured with
a different control module for altitude operation, but the
operation given in this manual remains the same as the
standard boilers. A high altitude label (as shown in FIG. A)
is also affi xed to the unit.

6. Ratings have been confi rmed by the Hydronics Section of

AHRI.

7

Maximum allowed working pressure is located on the rating plate.

NOTICE

Knight XL Boiler

AHRI Rating

Model Number

Note: Change “N” to

“L” for L.P. gas models.

Input
MBH

(Note 4)

Min Max

Gross

Output

MBH

(Note 1)

Net

AHRI

Ratings

Water,

MBH

(Note 2)

KBN400

80

399

373

324

KBN501

100

500

467

406

KBN601

120

600

567

493

KBN701

140

700

660

574

KBN801

160

800

752

654

Other Specifi cations

Boiler

Water

Content

Gallons

Water

Connections

Gas

Connections

Air

Size

Vent

Size

(Note 3)

3.4

1-1/2"

1"

4"

4"

4.2

1-1/2"

1"

4"

4"

4.2

2"

1"

4"

4"

5.0

2"

1"

4"

6"

5.7

2"

1"

4"

6"

Figure A High Altitude Label Location

UNIT EQUIPPED FOR

3000 FT. TO 12,000 FT.

HIGH ALTITUDE

7. Knight XL boilers comply with the requirements of CSD-1

Section CW-400 requirements as a temperature operation
control. The manual reset high limit provided with the
Knight XL is listed to UL353.

Installation & Operation Manual