Sidewall termination – optional concentric vent: Models 400 - 601 Only

Multiventing sidewall terminations

When two (2) or more direct vent appliances are vented
near each other, each appliance must be individually vented
(see FIG. 4-12). NEVER common vent or breach vent this
appliance. When two (2) or more direct vent appliances are
vented near each other, two (2) vent terminations may be
installed as shown in FIG. 4-12. It is important that vent
terminations be made as shown to avoid recirculation of fl ue
gases.

VENT

COMBUSTION
AIR

12"
MINIMUM

Figure 4-12 Concentric Vent and Combustion Air Termination

COMBUSTION AIR

VENT

VENT

COMBUSTION AIR

STRAP

(FIELD SUPPLIED)

ELBOW

(FIELD SUPPLIED)

Figure 4-11 Concentric Vent Sidewall Attachment

DO NOT use fi eld-supplied couplings
to extend pipes. Airfl ow restriction
will occur and may cause intermittent
operation.

8. Cement appliance combustion air and vent pipes to the

concentric vent termination assembly. See FIG. 4-11
for proper pipe attachment.

9. Operate the appliance one (1) heat cycle to ensure

combustion air and vent pipes are properly connected
to the concentric vent termination connections.