Installation & Operation Manual

The installer must use a specifi c vent starter
adapter at the fl ue collar connection.
The adapter is supplied by the vent
manufacturer to adapt to its vent system.
See Table 3F for approved vent adapters.
Discard CPVC starter piece.

NOTICE

All vent connections MUST be secured by
the vent manufacturer's joint connector
(FIG. 3-4).

NOTICE

IMG00128

JOINT CONNECTOR REQUIRED AT ALL
COMPONENT CONNECTIONS OF VENT SYSTEM

POLYPROPYLENE ADAPTER

Figure 3-4 Near Boiler Polypropylene Venting

Model

Centrotherm InnoFlue SW

Duravent Polypro

Polypropylene

Adapter

Joint

Connector

Sidewall Retaining

Bracket*

Sidewall Adapter*

Polypropylene

Adapter

Joint

Connector

Sidewall Kit*

400-601

ISAAL0404 IANS04

IATP0404

ISTAGL0404

4PPS-AD

4PPS-LB

4PPS-HLK

701-801

ISAAL0606

Not

Required

IATP0606

ISTAGL0606

FSA-6PVCM-6PPS Not Required

6PPS-HLK

* These parts are only needed if the sidewall termination assembly is used (see FIG. 4-5B on page 26).

Table 3F Approved PolypropyleneTerminations

Polypropylene

This product has been approved for use with polypropylene
vent with the manufacturers listed in Table 3E.

All terminations must comply with listed options in this manual
and be a single-wall vent offering.

For use of fl ex pipe, it is recommended to have the vent material
in 32°F or higher ambient space before bending at installation.
No bends should be made to greater than 45° and ONLY
installed in vertical or near vertical installations.

For support and special connections required, see the
manufacturer's instructions. All vent is to conform to standard
diameter and equivalent length requirements established.

Use only the adapters and vent system listed
in Tables 3E and 3F. DO NOT mix vent
systems of different types or manufacturers.
Failure to comply could result in severe
personal injury, death, or substantial
property damage.

ƽ WARNING

Installations must comply with applicable
national, state, and local codes. For
Canadian installation, polypropylene vent
must be listed as a ULC-S636 approved
system.

NOTICE

Installation of a polypropylene vent system
should adhere to the vent manufacturer’s
installation instructions supplied with the
vent system.

NOTICE

Approved Polypropylene Vent Manufacturers

Make

Model

Centrotherm Eco Systems

InnoFlue SW/Flex

Duravent (M & G Group)

PolyPro Single-Wall / PolyPro Flex

Table 3E Polypropylene Vent Pipe and Fittings

ƽ WARNING

Insulation should not be used on
polypropylene venting materials. The use
of insulation will cause increased vent wall
temperatures, which could result in vent
pipe failure.