Sidewall direct venting – Lochinvar Commercial Soiler 400-801 User Manual

Page 27

background image

27

4

Sidewall direct venting

(continued)

4" (102 MM) DIA.

6" (152 MM) DIA.

RAIN CAP

"Y" CONCENTRIC
FITTING

"FLEXIBLE" PIPE
COUPLING

6" (152 MM) DIA.

6" (152 MM) DIA.

6" (152 MM) TO 4" (102 MM) REDUCER

Figure 4-8 Kit Contents_CVK3007 - Models 400 - 601

Sidewall termination installation

1. Determine the best location for the termination kit

(see FIG. 4-7).

2. Reference

the

Determine Location Section on page 23 of

this manual for general termination considerations.

3. Cut one (1) hole (7 inch (178 mm) diameter for #CVK3007

installations into the structure to install the termination kit.

4. Partially assemble the concentric vent termination kit.

Clean and cement using the procedures found in these
instructions.

a. Cement the Y concentric fi tting to the larger kit pipe
(FIG.

4-8).

b. Cement the rain cap to the smaller diameter kit pipe
(FIG.

4-8).

Sidewall termination – optional concentric vent: Models 400 - 601 Only

Description and usage

Lochinvar offers an optional concentric combustion air
and vent pipe termination kit (#CVK3007 for 4" (102 mm)
diameter - Models 400 - 601). Both combustion air and vent
pipes must attach to the termination kit. The termination kit
must terminate outside the structure and must be installed as
shown below in FIG. 4-7.

The required combustion vent pipe materials are listed in
Table 3D, on page 20 of this manual.

OVERHANG
OR ROOF

12" (305 MM)

MIN

12" (305 MM)

MIN

GRADE / SNOW LINE

Figure 4-7 Concentric Sidewall Termination - Models
400 - 601

Installation & Operation Manual