Table 3B Inlet/Outlet System Sensor Resistance vs. Temperature

Temperature

Resistance

50

18,780

68

12,263

86

8,194

104

5,592

122

3,893

140

2,760

Checking temperature sensors

The pool heater temperature sensors (inlet and outlet water) are both resistance type devices. The following table shows the
correct values for the sensors at various temperatures. Use an ohmmeter to read the resistance of the sensor at a known
temperature. If the resistance of the sensor does not closely match, replace the sensor.