Table 3B Inlet/Outlet System Sensor Resistance vs. Temperature
Temperature
Resistance
50
18,780
68
12,263
86
8,194
104
5,592
122
3,893
140
2,760
Checking temperature sensors
The pool heater temperature sensors (inlet and outlet water) are both resistance type devices. The following table shows the
correct values for the sensors at various temperatures. Use an ohmmeter to read the resistance of the sensor at a known
temperature. If the resistance of the sensor does not closely match, replace the sensor.
3
Troubleshooting
(continued)
Service Manual
23
See also other documents in the category Lochinvar Water boiler:
- KNIGHT XL KBN800 (6 pages)
- SD (2 pages)
- Copper Fin II CF-1261 (1 page)
- EBS-SUB-02 (2 pages)
- Commercial Water Heater (2 pages)
- 999 - 750 (72 pages)
- JR-SUB-07 (2 pages)
- POWER-FIN PB/PF 2001 (4 pages)
- Squire SSS041 (20 pages)
- Knight Heating Boiler 81-286 (48 pages)
- 1302 (2 pages)
- CH/CF/CP 300-750 (4 pages)
- 000 (80 pages)
- Copper-fin CW-360 (1 page)
- CP-5M-4/08 (52 pages)
- 500 (68 pages)
- 000 - 260 (52 pages)
- 000 - 260 (52 pages)
- TNR-I&S-02 (20 pages)
- ARMOR 150 - 800 (36 pages)
- KNIGHT KB-500 (1 page)
- PB 502 thru 1302 (4 pages)
- PB-1302(M9) (1 page)
- MDN 030 (2 pages)
- 495 (52 pages)
- Hot Water Generator (24 pages)
- Heating Boilers KB 400 thru 801 (4 pages)
- SYNO 1.3 (16 pages)
- SQUIRE SIT119 (24 pages)
- Commercial Gas Glass Lined Tanke Type Water Heater CG200 (28 pages)
- COPPER-FIN CB-0745 (1 page)
- 0402-0752 (2 pages)
- 1.3 (56 pages)
- RPV-I&S (16 pages)
- KNIGHT 400 (48 pages)
- KNIGHT 210 (20 pages)
- Power Fin PF-0502 (M9) (2 pages)
- COPPER-FIN II 402 - 2072 (16 pages)
- 752 (16 pages)
- WATER HEATERS (12 pages)
- EFFICIENCY+ E B N 150 (2 pages)
- Sync Condensing Boiler 1.5 (56 pages)
- EB 150 -- 300 (4 pages)
- CW495-2066 (2 pages)
- CREST 2.5 (60 pages)