Maintenance, Maintenance and annual startup, Service technician – Lochinvar EnergyRite ER402 User Manual

Page 13: Owner maintenance

background image

2

Maintenance

Service Manual

13

Maintenance and annual startup

Table 2A Service and Maintenance Schedules

Service technician

(see the following pages for instructions)

General:

• Address reported problems

• Inspect interior; clean and vacuum if

necessary

• Check for leaks (water, gas, and flue)

• Verify flue and air lines in good

condition and sealed tight

• Check control settings per the Access

Setup Menu section of this manual

• Check ignition and flame sense

electrodes (sand off any deposits;
clean and reposition)

• Check wiring and connections

• Perform start-up checkout and

performance verification per Section 9
in the EnergyRite Installation and
Operation Manual.

• Flame inspection (stable, uniform)

If combustion or performance
indicate need:

• Clean burners

• Clean heat exchanger

ANNUAL

ST

ART

-UP

Owner maintenance

(see the EnergyRite User’s Information Manual for

instructions)

Daily

• Check pool heater area

Monthly

• Check vent piping

• Check air inlet piping (if

applicable)

• Check relief valve (if applicable)

Periodically

• Test low water cutoff (if used)

• Reset button (low water cutoff)

Every

6 months

• Check pool heater piping (gas

and water) for leaks

• Operate relief valve (if

applicable)

End

of season

• Shut the pool heater down and

winterize if location is subjected
to freezing temperatures, see the
Winterizing on page 21 of this
manual