beautypg.com

Maintenance, Burner removal and cleaning, Check ignition ground wiring – Lochinvar EnergyRite ER402 User Manual

Page 15: Check all pool heater wiring, Inspect ignition and flame sense electrodes, Check burner flame

background image

Service Manual

15

2

Maintenance

(continued)

Figure 2-2_Gas Train and Burners

Burner removal and cleaning

ƽ

ƽ WARNING The area around the burner viewport is

hot and direct contact could result in
burns.

Figure 2-1_Flame Pattern Illustration

a)

Normal Flame: A normal flame is blue, with slight
yellow tips, with a well defined inner cone and no
flame lifting.

b) Yellow Tip: Yellow tip can be caused by blockage or

partial obstruction of air flow to the burner(s).

c)

Yellow Flames:

Yellow flames can be caused by

blockage of primary air flow to the burner(s) or
excessive gas input.

This condition MUST be

corrected immediately.

d) Lifting Flames: Lifting flames can be caused by over

firing the burner(s), excessive primary air or high
draft.

Check ignition ground wiring

1. Inspect pool heater ground wire from the combustion

chamber door to the ground terminal on the control
module.

2. Verify all wiring is in good condition and securely

attached.

3. Check ground continuity of wiring using continuity

meter.

4. Replace ground wires if ground continuity is not

satisfactory.

Check all pool heater wiring

1. Inspect all pool heater wiring, making sure wires are in

good condition and securely attached.

Inspect ignition and flame sense
electrodes

1. Remove the ignition and flame sense electrodes from

the combustion chamber door.

2. Remove any deposits accumulated on the ignition/flame

sense electrode using sandpaper.

If the electrodes

cannot be cleaned satisfactorily, replace with new ones.

3. Replace ignition/flame sense electrode, making sure

gasket is in good condition and correctly positioned.

Check burner flame

Visually check main burner flames at each start up after long
shutdown periods or at least every six months.

A

burner viewport is located on the right side of the pool
heater, below the water connections on the front header.
Remove cap to view flame.