Troubleshooting – Lochinvar CREST 3 User Manual
Page 41
3
Troubleshooting
(continued)
Service Manual
41
Table 3G (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
FAULT
DESCRIPTION
CORRECTIVE ACTION
Anti-cycling
The main control board has received a call
for heat too quickly after the previous call for
heat has ended.
• The control board will release the call for heat after a
set time period.
• The control board will release the call for heat if the
outlet temperature drops too quickly.
Flame Failure
Ignition
(will require a manual
reset once the condition
has been corrected.
Press the RESET button
on the SMART TOUCH
display to reset.)
The unit has failed to prove main burner
ignition. It will require a manual reset before
attempting to fire again.
• Inspect spark electrode and associated wiring for
damage and connection. Reference page 34 of this
manual for removal and cleaning procedures.
Replace if necessary.
• Visually check for presence of a spark from the view
port.
• Check for proper electrical grounding of the unit.
• Check incoming supply gas pressure. Natural and
LP gas pressures should be between 4 - 14 inches w.c.
(1.0 - 3.5 kPa). Refer to Section 6 - Gas Connections
of the Crest Installation and Operation Manual for
detailed information concerning the gas supply.
• Verify that the plastic hose from gas valve 1 to the air
inlet is connected and is not damaged.
• Verify that the vent/air intake pipes are correctly
installed and that there are no obstructions.
• If 120 vac is present at the main control board, check
the wiring between the main control board and the gas
valve. Replace the wiring if necessary. Do not
disconnect the wiring from the gas valve and attempt to
measure voltage at that point. The main control board
can detect if the gas valve is not connected and will
display the Gas Valve / Connection fault.
• If 120 vac is present, check the outlet of the valve to
ensure the valve is flowing gas. With a manometer
connected to the outlet tap of the gas valve, when the
unit is in the prepurge period, there should be a
negative pressure present. When the valve is
energized a change in pressure should occur. If the
pressure change does not occur, the gas valve is not
opening. Replace the gas valve.
•
Inspect flame sensor and associated wiring.
Reference page 34 of this manual for removal and
cleaning procedures. Replace if necessary.
• Inspect the burner. Reference page 34 of this manual
for removal and cleaning procedures. Replace if
necessary.