Troubleshooting, Checking temperature sensors – Lochinvar CREST 3 User Manual

Page 38

background image

3

Troubleshooting

38

Service Manual

Table 3B - Inlet Water/System Sensor Resistance vs.
Temperature

Temperature Resistance Temperature Resistance

50

18,780

158

1,990

68

12,263

176

1,458

86

8,194

194

1,084

104

5,592

212

817

122

3,893

140

2,760

Table 3C - Outdoor Air Sensor Resistance vs. Temperature

Temperature Resistance Temperature Resistance

-50

490,813

20

46,218

-40

336,606

30

34,558

-30

234,196

40

26,099

-20

165,180

50

19,900

10

118,018

60

15,311

0

85,362

70

11,883

10

62,465

80

9,299

Checking temperature sensors

The boiler temperature sensors (inlet water, outlet water, system water, flue, and outdoor air) are all resistance type devices. The
following tables show the correct values for the sensors at various temperatures. Use an ohmmeter to read the resistance of the
sensor at a known temperature. If the resistance of the sensor does not closely match its corresponding table, replace the sensor

It is important to note that the flue and outlet inlet air - S11/S13 #1 and S12/S14 #2 water sensors have two temperature sensing
devices in one housing. These devices are designated as S1/S9, outlet sensor and S3/S10, flue sensor. Please reference the wiring
diagram in the Crest Installation and Operation Manual for correct terminal location.

Outlet

S1

R/Y

Outlet

S9

RW/Y

Pre-Mix Air 1

S11

GY/Y

Pre-Mix Air 1

S13

BR/Y

Pre-Mix Air 2

S12

BK/Y

Pre-Mix Air 2

S14

T/Y

Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance

50

19,553

158

2,004

50

40,030

158

3,478

68

12,690

176

1,464

68

25,030

176

2,492

86

8,406

194

1,084

86

16,090

194

1,816

104

5,715

212

816

104

10,610

212

1,344

122

3,958

122

7,166

140

2,786

140

4,943

Table 3D - Outlet Water Sensor Resistance vs. Temperature

Flue

S3

GY/Y

Flue

S10

W/Y

Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance

50

40,030

158

3,478

50

258,500

158

16,870

68

25,030

176

2,492

68

125,500

176

12,000

86

16,090

194

1,816

86

80,220

194

8,674

104

10,610

212

1,344

104

52,590

212

6,369

122

7,166

122

35,270

140

4,943

140

24,160

Table 3E - Flue Sensor Resistance vs. Temperature

This manual is related to the following products: