Service

Service Manual

14

Parameter table

Table 1B (continued from previous page) This table lists SMART TOUCH control module parameters and where to
access them

Menu Sub

Item

Parameter Name

(as shown on the LCD screen)

See

Page

Min

Max

Default

User

Installer

Value

Value

Value Access

Access

C

7

Boost Time

20

0

250

20

No

Yes

8

Boost Temperature

20

0

25

0

No

Yes

9

Shift OA Reset Curve

20

-27

27

0

No

Yes

D

1

Ramp Delay Mode

20

N/A

N/A

N/A

No

Yes

2

Ramp Delay Time #1

20

1

40

2

No

Yes

3

Ramp Delay Time #2

20

1

40

2

No

Yes

4

Ramp Delay Time #3

20

1

40

2

No

Yes

5

Ramp Delay Time #4

20

1

40

1

No

Yes

6

Ramp Delay Time #5

20

1

40

1

No

Yes

7

Ramp Delay Time #6

20

1

40

1

No

Yes

8

Ramp Delay Limit #1

20

10

100

20

No

Yes

9

Ramp Delay Limit #2

20

10

100

30

No

Yes

10

Ramp Delay Limit #3

20

10

100

40

No

Yes

11

Ramp Delay Limit #4

20

10

100

55

No

Yes

12

Ramp Delay Limit #5

20

10

100

75

No

Yes

13

Ramp Delay Limit #6

20

10

100

100

No

Yes

E

1

BMS Active/Inactive

21

ACTIVE INACTIVE INACTIVE

No

Yes

2

BMS Mode

21

POWER SETPOINT

POWER

No

Yes

3

BMS Volts at Min Rate

21

0

10

2

No

Yes

4

BMS Volts at Max Rate

21

0

10

10

No

Yes

5

BMS Rate at Min Volts

21

4

100

4

No

Yes

6

BMS Rate at Max Volts

21

0

100

100

No

Yes

7

BMS Volts at Min Setpoint

21

0

10

2

No

Yes

8

BMS Volts at Max Setpoint

21

0

10

10

No

Yes

9

BMS Setpoint at Min Volts

21

32

185

68.9

No

Yes

10

BMS Setpoint at Max Volts

21

32

185

178.7

No

Yes

11

BMS Volts to Enable

21

0

10

2

No

Yes

12

Differential to Stop BMS Demand

21

0

10

0.5

No

Yes

13

BMS Enable Mode

21

ENABLE VOLTAGE VOLTAGE

No

Yes

OUTDOOR

RESET

RAMP DELA

Y

BMS