Installation and Service Manual

Refer to Circulating Pump on page 46 for information relating to
pump wiring.

TABLE-P

AMP Draw Data

Btu/Hr

Input

Controls

Fans

Pump

Approximate

Total Amps

500,000

3.6

2.7

5.0

11.3

650,000

5.4

3.4

5.0

13.8

750,000

5.4

3.4

5.0

13.8

990,000

7.3

3.2

7.4

17.9

1,260,000

7.3

3.2

7.4

17.9

1,440,000

7.3

6.7

7.4

21.4

1,800,000

7.3

6.7

8.8

22.8

2,070,000

7.3

6.7

8.8

22.8

45

Pipe Size Requirements

The pipe sizing chart provides the minimum pipe size for common
manifold piping to ensure adequate flow.

TABLE-Q

Pipe Sizing Chart

500,000 - 750,000 Btu/hr Models

Number of Units

Common Pipe

Size (Min.)

1

2"

2

3"

3

3 1/2"

4

4"

5

5"

6

5"

990,000 - 2,070,000 Btu/hr Models

Number of Units

Common Pipe

Size (Min.)

1

2 1/2"

2

4"

3

4"

4

5"

5

6"

6

6"