1-9. Tubing Length
Table 1-16 Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights
R410A distribution joint
APR-P160BA (for indoor unit)
Note: Do not use commercially available T-joints for the liquid tubing.
H2
LD
L1
L2
LC
LB
LA
* Be sure to use special R410A distribution joints (APR: purchased separately) for outdoor
unit connections and tubing branches.
Main tube of unit
1st branch
Unit distribution tube
1
2
3
n-1
n
L3
H1
Items
Marks
Contents
Length (ft.)
L1
Max. tubing length
Actual length
492
Equivalent length
574
L (L2 – L3)
Difference between max. length and min.
131
length from the No.1 distribution joint
1
,
2
...
n
Max. length of each distribution tube
98
1
+
2
+...
n–1
Total max. tubing length including length of
656
each distribution tube (only narrow tubing)
H1
When outdoor unit is installed higher than indoor unit
164
When outdoor unit is installed lower than indoor unit
131
H2
Max. difference between indoor units
49
L = Length, H = Height
Allowable tubing
length
>
>
Allowable elevation
difference
>
>
>
>
>
>
+L1
Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown
in the figure below.