GP Series Portable Chillers

Chapter 4: Operation

30 of 44

the

to accept the password. The following screen will appear.

Figure 9 - Operator Setpoints Screen

3. Depress

to move the cursor to the Leaving Temp line. Use the

or

button to increment or decrement the value. Depress

to accept the

value and move the cursor down one line.

4. Adjust the Hi Temp Warning and Hi Temp Fault in the same manner.

5. Depress the

button twice to return to the main status screen.

4-6 Alarms

The controller is setup with multiple alarms, most of them configurable using the Supervisor
password. Section 4-5 Controller Setpoints gives a list of alarms that the controller is setup to
display. The alarms are broken up into two categories – warnings and faults. The warning
notifies the user that the parameter has been exceeded and the chiller is allowed to keep
operating, but should be monitored to determine the cause of the warning. The fault notifies
the user that the parameter has been exceeded and the chiller and pump has been shut down to
protect the system.

4-7 Optional

Communications

The communications function allows you to monitor and set the parameters by a program
prepared and running on a host computer connected to the controller.

When using the communications function, you must add on the unit for RS-485 Modbus
communications. The communications function allows you to read/write parameters, do
operating instructions, and select the setting level.