Chapter 4: Operation

28 of 44

4-5 Controller

Setpoints

Access Level

Variable Description

Operator Supervisor

Leaving Temp

Temperature of fluid out to process

x

x

Hi Temp Warning

Setpoint for alarm to warn when leaving fluid
temperature is too high

x x

Hi Temp Fault

Setpoint to shut down pump and compressor based on
leaving fluid temperature

x x

Compressor On
Differential

Temperature Difference between Leaving Fluid
Temperature and Setpoint to turn on the compressor

x

Compressor Off
Differential

Temperature Difference between Leaving Fluid
Temperature and Setpoint to turn off the compressor

x

Pump Stop Delay

Delay time in seconds between fault and stopping the
pump

x

Low Temperature
Warning

Temperature to activate Low Temperature Warning
alarm

x

Low Temperature Fault

Temperature to activate Low Temperature Fault alarm

x

Water Make-up On

The tank level to turn on optional water make-up valve;
based on size of tank

x

Water Make-up Off

The tank level to turn off optional water make-up valve;
based on size of tank.

x

Water Make-up Time

The time in seconds that controller will allow for filling
the tank

x

Low Level Warning

Tank level that will activate Low Level Warning alarm

x

Low Level Fault

Tank level that will activate Low Level Warning fault

x

High Level Warning

Tank level that will activate High Level Warning alarm

x

High Level Fault

Tank level that will activate High Level Warning fault

x

High Temperature
Delay

Delay time in minutes between fault and stopping the
compressor and pump

x

Alarm Silence Time

Time in minutes to silence alarm (with optional audible
alarm). After time alarm will reactivate.

x

Operator Password
Time

Time in minutes for operator password to be active

x

Supervisor Password
Time

Time in minutes for supervisor password to be active

x