beautypg.com

2 initial start-up – Sterling GP Series User Manual

Page 23

background image

GP Series Portable Chillers

Chapter 4: Operation

23 of 44

4-2 Initial

Start-up

1. Verify the initial start-up checklist from Chapter 3, Section 3-11.
2. With the main supply power switch in the ON position, the screen will

display the version of the software for a period of 5 seconds, and then display
the main status screen.

Figure 4 - Main Status Screen

3. Set the Leaving Fluid temperature by depressing the

button to display

the menu.

Figure 5 - Menu Screen

4. Depress the

or

button to highlight SETPOINTS and press

. If

passwords were setup (See Section 3-12 for information on the controller
passwords) the password screen will appear.