Siemens BACnet ATEC 125-5050 User Manual
Page 28
Chapter 3 – Point Database
28
Siemens Industry, Inc.
BACnet ATEC Owner's Manaul
125-5050, Rev. AA
4/20/2010
Descriptor
Address
1
Application
Description
FLOW
{75}
2
All
except 2597
Indicates the amount of air currently passing the air velocity
sensor. The value is calculated as a percentage based on
where the value of AIR VOLUME is in the range between 0
and CTL FLOW MAX.
CTL FLOW MIN
{76}
2
All
except 2597
The active minimum flow used as a limit for the flow control
loop. This value is the same as CLG FLOW MIN if the
controller is in cooling mode, or is the same as HTG FLOW
MIN if the controller is in heating mode, unless it is overridden.
CTL FLOW MAX
{77}
All
except 2597
The active maximum flow used as a limit for the flow control
loop. This value is the same as CLG FLOW MAX if the
controller is in cooling mode, or is the same as HTG FLOW
MAX if the controller is in heating mode unless, it is
overridden.
CTL TEMP
{78}
All
except 2597
The temperature used as input for the temperature control
loops. This value is the same as the value in ROOM TEMP
and RM TEMP OFFSET unless it is overridden.
CLG LOOPOUT
{79}
All
except 2597
The cooling temperature control loop output value in percent.
HTG LOOPOUT
{80}
All
except 2560, 2597 The heating temperature control loop output value in percent.
AVG HEAT OUT
{81}
2
2562, 2564, 2566
This point is used to determine what stages of electric heat
are used for a given loop output value. The ranges for the
value are determined by the number of stages used: 0 to 100
for 1 stage of electric heat, 0 to 200 for 2 stages of electric
heat, and 0 to 300 for 3 stages of electric heat.
With electric heat, this value is equal to: HTG LOOPOUT ×
STAGE COUNT.
STAGE MAX
82
2562, 2564, 2566
The value, in percent, which the heating loop must exceed for
the electric heat to be ON for the full duty cycle (STAGE
TIME).
STAGE FAN
83
2565, 2567
The valve must be opened greater than this value before the
fan will turn ON.
STAGE MIN
83
2562, 2564, 2566
The value, in percent, which the heating loop must go below
for the electric heat to be OFF for the full duty cycle (STAGE
TIME).
DMPR STATUS
{84}
2
2560, 2561, 2562,
2563
This point is used only when CAL MODULE set to YES. It
readjusts the damper position if the command value is not
equal to the actual position of the damper. CAL indicates that
the damper is operating normally. RECAL indicates that the
damper position was adjusted (recalibrated) by 25% because
the desired airflow was not obtainable under its current status.
SWITCH LIMIT
85
All
except
2560, 2561, 2597
The active temperature control loop output must be less than
this value to switch between cooling mode and heating mode.
Actual switchover depends on SWITCH DBAND being
exceeded and is subject to SWITCH TIME being expired.
SWITCH TIME
86
All
except
2560, 2561, 2597
The time, in minutes, before the heat/cool mode can change
over when the other parameters are appropriate.
STAGE COUNT
88
2562, 2564, 2566
The number of electric heating stages used by the application.
DOs associated with unused stages may be used as spare
DOs.
VALVE COUNT
88
2563
The number of heating valves available.
STAGE TIME
89
2562, 2564, 2566
The cycle time in minutes for the electric reheat stages. For
example, if there are three stages of electric heat and STAGE
TIME = 10 minutes, STAGE COUNT = 3, and AVG HEAT
OUT = 150% then, Stage 1 is ON for 10 minutes (100% of the
time), Stage 2 is ON for 5 minutes (50% of 10 minutes) and