beautypg.com

Baseboard radiation, Electric heat interlock, Application 2863 vav with hot water reheat – Siemens BACnet ATEC 125-5050 User Manual

Page 18

background image

Chapter 2 – Applications

18
Siemens Industry, Inc.

BACnet ATEC Owner's Manaul

125-5050, Rev. AA

4/20/2010

Baseboard Radiation

Baseboard radiation can be a two-position valve or electrical resistance heating.
If the controller is in cooling mode, the heating valve is closed. When in heating mode,

the controller will operate the heating valve to maintain the heating setpoint.

Electric Heat Interlock

CAUTION

Do not set EHEAT FLOW (the defined minimum) to less than 5%; otherwise, the
electric heat interlock will be disabled.

The electric heat stages will be disabled (turned off) when the electric heat airflow is

less than the defined minimum.

Application 2863 VAV with Hot Water Reheat

In Application 2863, the controller modulates the supply air damper of the terminal box

for cooling and controls a hot water valve or baseboard radiation for heating. When in

heating, the terminal box either maintains minimum airflow or modulates the supply air

damper. In order for the terminal box to work properly, the central air-handling unit

must provide supply air for cooling.
See the following figures.