beautypg.com

Chapter 3 – point database – Siemens BACnet ATEC 125-5050 User Manual

Page 24

background image

Chapter 3 – Point Database

24
Siemens Industry, Inc.

BACnet ATEC Owner's Manaul

125-5050, Rev. AA

4/20/2010

Chapter 3 – Point Database

Chapter 3 presents a description of the BACnet VAV Controller — Electronic Output

point database, including point descriptors, point addresses, and a listing of

applications in which each point is found.

Descriptor

Address

1

Application

Description

CTLR ADDRESS

01

All

Identifies the controller on the FLN trunk.

APPLICATION

02

All

Identification number of the program running in the controller.

RMTMP OFFSET

03

All

Compensates for deviations between the value of ROOM

TEMP and the actual room temperature. This corrected value

is displayed in CTL TEMP. RMTMP OFFSET + ROOM TEMP

= CTL TEMP

ROOM TEMP

{04}

2

All

Actual reading from the room temperature sensor.

HEAT.COOL

{05}

All

except

2560, 2597

Current mode of operation for applications that can be in

either a heating mode or a cooling mode.

DAY CLG STPT

06

All

except 2597

The temperature setpoint in degrees that the controller

maintains during day periods in cooling mode if a room

temperature sensor setpoint dial is not present or is not used.

See STPT DIAL.

DAY HTG STPT

07

All

except 2560, 2597 The temperature setpoint in degrees that the controller

maintains during day periods in heating mode if a room

temperature sensor setpoint dial is not present or is not used.

See STPT DIAL.

NGT CLG STPT

08

All

except 2597

The temperature setpoint in degrees that the controller

maintains during the night periods in cooling mode.

NGT HTG STPT

09

All

except 2560, 2597 The temperature setpoint in degrees that the controller

maintains during the night periods in heating mode.

RM STPT MIN

11

All

except 2597

The minimum temperature setpoint in degrees that the

controller can use from the setpoint dial. This overrides any

temperature setpoint from the setpoint dial that falls below this

minimum.

RM STPT MAX

12

All

except 2597

The maximum temperature setpoint in degrees that the

controller can use from the setpoint dial. This overrides any

temperature setpoint from the setpoint dial that falls above this

maximum.

RM STPT DIAL

{13}

2

All

The temperature setpoint in degrees from the room

temperature sensor (not available on all temperature sensor

models). This setpoint will be used for control in day mode

(heating or cooling) when enabled by STPT DIAL.

STPT DIAL

14

All

except 2597

YES indicates that there is a room setpoint dial on the room

temperature sensor and it should be used as the temperature

setpoint for control in day/occupied mode. NO indicates that

the appropriate preset setpoint will be used as the

temperature setpoint for control in day/occupied heating or

cooling mode. Valid input: YES or NO.

AUX TEMP UI 1

{15}

All except 2561

Actual reading from a 10K thermistor connected to the

controller's Ul 1 input. When a thermistor is connected at Ul 1,

UI 1 is not available. See UI 1.

SUPPLY TEMP

{15}

2561

Actual reading from a 10K thermistor connected to the