Siemens BACnet ATEC 125-5050 User Manual
Page 25
Chapter 3 – Point Database
25
Siemens Industry, Inc.
BACnet ATEC Owner's Manaul
125-5050, Rev. AA
4/20/2010
Descriptor
Address
1
Application
Description
controller's Ul 1 input. The controller uses this value to
determine whether it is in heating or cooling mode.
FLOW START
16
All
except
2560, 2561, 2597
Determines how the damper modulation will be sequenced
while in heating mode. When HTG LOOPOUT is above this
value, then FLOW STPT starts to increase.
FLOW END
17
All
except
2560, 2561, 2597
Determines how the damper modulation will be sequenced
while in heating mode. When HTG LOOPOUT is below this
value, then FLOW STPT starts to decrease.
WALL SWITCH
18
All
YES indicates that the controller is to monitor the status of a
wall switch that is connected to UI 2. NO indicates that the
controller will not monitor the status of a wall switch, even if
one is connected. Valid input: YES or NO.
DI OVRD SW
{19}
2
All
Actual indication of the status of the override switch (not
physically available on all temperature sensor models) at the
room temperature sensor. ON indicates that the switch is
being pressed. OFF indicates that the switch is released.
Valid input: ON or OFF.
OVRD TIME
20
All
except
2597
The amount of time in hours that the controller will operate in
day/occupied mode when the override switch is pressed while
the controller is in night/unoccupied mode.
NGT OVRD
{21}
2
All
except
2597
Indicates the mode that the controller is operating in with
respect to the override switch. NIGHT indicates that the switch
has not been pressed and the override timer is not active.
DAY indicates that the switch has been pressed and the
override timer is active. The controller then uses a day mode
temperature setpoint. This point is only in effect when
DAY.NGT indicates night mode.
REHEAT START
22
All
except
2560, 2561, 2597
Determines how the reheat modulation will be sequenced
while in heating mode. When HTG LOOPOUT is above this
value, then the reheat modulates upward.
REHEAT END
23
All
except 2560, 2561,
2597
Determines how the reheat modulation will be sequenced
while in heating mode. When HTG LOOPOUT is below this
value, then the reheat modulates downward.
DIGITAL UI 2
{24}
All
Actual status of a contact connected to the controller at UI 2.
ON indicates that the contact is closed; OFF indicates that the
contact is open. If a wall switch is used, it is connected to UI
2. See WALL SWITCH.
DIGITAL UI 1
{25}
2
All
except
2561
Actual status of a contact connected to the controller UI 1. ON
indicates that the contact is closed; OFF indicates that the
contact is open. When a contact is connected as a digital
input, the analog input is not available. See AUX TEMP.
SERIES ON
26
2564, 2565
When flow rises above this value, the series fan will turn ON.
SERIES OFF
27
2564, 2565
When flow drops below this value and other conditions have
been met, the series fan will turn OFF.
PARALLEL ON
28
2566, 2567
When flow drops below this value and other conditions have
been met, the parallel fan will turn ON.
DAY.NGT
{29}
All
Indicates the mode in which the controller is operating. Day
temperature setpoints will be used in day mode. Night
temperature setpoints will be used in night mode. This point is
normally set by the field panel.
PARALLEL OFF
30
2566,
2567
When flow rises above this value, the parallel fan will turn
OFF.
CLG FLOW MIN
31
All
except 2597
The minimum amount of air in CFM (LPS) to be supplied to