beautypg.com

Sentry – Slant/Fin SENTRY SX-210 User Manual

Page 7

background image

B. 1. This device must be installed after the boiler draft hood

(between the draft hood outlet and the connector to the out-

door chimney or vent) as close to the draft hood as practi-

cable, and without modification of the draft hood or the vent

damper. (See figures 1, 2 and 3.)

2. The inlet size of the vent damper must be the same nomi-

nal trade size as the outlet of the draft hood.

3. This device must be located in a venting system or section

of a venting system so that it serves only the single appli-

ance for which it is installed. (See figure 4.)

4. Clearances of not less than 6 inches (152MM) must be

maintained from combustible materials, with provisions for

service access.

C. NOW, PROCEED AS FOLLOWS:

Remove the cover from the aquastat control. Note the Molex

connector (MALE PLUG) inside the control box (see figure 6).

Remove knockout in the control housing marked for vent

damper, pass “Receptacle B” of vent damper harness through

the knockout and attach the flexible metallic connector to the

control housing with the nut. Join the two halves of the Molex

connector (MALE PLUG AND RECEPTACLE B). Replace the

control cover. Attach the other side of vent damper harness to

vent damper operator (if not attached) and connect Molex con-

nector to operator receptacle. (See figures 1 and 2.)

D. AFTER INSTALLATION:

1. Operate system through two complete cycles to check for

opening and closing in proper sequence, and proper burn-

er operation. DAMPER MUST BE IN OPEN POSITION

WHEN BOILER MAIN BURNERS ARE OPERATING.

2. Perform installation checks as required by ANSI specifica-

tion Z21.66. (See Vent Damper Instructions.)

3. Check the troubleshooting section if problems arise with the

installation.

E. THERMOSTAT HEAT ANTICIPATOR ADJUSTMENTS

If the 24V room thermostat that controls this boiler has an

adjustable heat anticipator and has previously been adjusted

without a vent damper, then see publication VD-40 for correct

electrical requirement adder for the vent damper used. If room

thermostat has not been adjusted, connect entire system to

thermostat and run the system while measuring the current

drawn through the thermostat wires. Set the heat anticipator

at the value of current measured. For more information, see

Slant/Fin vent damper installation manual, pub. VD-40, and the

manufacturer's vent damper booklet shipped with the vent

damper.

GAS PIPING—
A. Local installation codes apply. The pipe joint compound used

on threads must be resistant to the action of liquefied petro-

leum gases.

B. The gas supply line to the boiler should be run directly from

the meter for natural gas or from the fuel tank for L.P.

propane gas. See page 2 for location of union and manual

main shutoff valve that may be specified locally.

Selecting pipe size for natural gas:

1. Measure or estimate the length of piping from the meter

to the installation site.

2. Consult gas supplier for heating value of gas (Btu/cu. ft.).

3. Divide boiler rated input by heating value to find gas flow

in piping (cu. ft. per hour).

4. Use table A to select proper pipe size.

Example: Boiler model S-150 is to be installed. Distance

from gas meter to the boiler is 30 ft. Heating value of natur-

al gas is 1020 Btu/cu. ft. Select proper pipe size.

Gas flow = 150,000 Btu/hour = 147 cu. ft. per hour

1020 Btu/cu.ft.

At 30 ft. length of pipe, match required capacity from Table A

(choose higher capacity, in this case is 152 cu. ft. per hour).

Required pipe size is 3/4".

Improper gas pipe sizing will result in pilot flame outages,

insufficient heat and other installation difficulties. For more

information and also if other appliances are to be attached

to the piping system, see Appendix C of National Fuel Gas

Code ANSI Z223.1-latest edition.

C. The boiler and its gas connection must be leak tested before

placing the boiler in operation. Use liquid soap solution for

all gas leak testing. DO NOT use open flame.

This boiler and its individual shutoff valve must be discon-

nected from the gas supply piping system during any pres-

sure testing of that system at test pressures in excess of 1/2

PSIG.

This boiler must be isolated from the gas supply piping sys-

tem by closing its individual manual shutoff valve during any

pressure testing of the gas supply piping system at test

pressures equal to or less than 1/2 PSIG.

D. All gas piping used should be inspected thoroughly for

cleanliness before makeup. A sediment trap must be pro-

vided, as illustrated on page 2.

E. The minimum and maximum gas supply pressure (at the

inlet of gas valve) are shown on the boiler rating plate for the

type of gas used. Gas supply pressure should never be less

than minimum or more than maximum pressure when the

boiler or any other appliance is turned on or off.

1/2

3/4

1

1-1/4

1-1/2

10

132

278

520

1050

1600

20

92

190

350

730

1100

30

73

152

285

590

890

40

63

130

245

500

760

50

56

115

215

440

670

60

50

105

195

400

610

70

46

96

180

370

560

80

43

90

170

350

530

90

40

84

160

320

490

100

38

79

150

305

460

Length
of Pipe

in Feet

Gas Flow In Piping --

cu. ft. per hr.

Iron Pipe Size (IPS)—inches

At pressure drop of 0.3 in. water, specific gravity = 0.60.

7

Sentry

ELECTRICAL CONTROLS AND WIRING—
A. The electrical power to the boiler must be on a separately

fused and live circuit.

B. If an external electrical source is utilized, the boiler, when

installed, must be electrically grounded in accordance with

the requirements of the authority having jurisdiction or, in

absence of such requirements, with the National Electrical

Code, ANSI/NFPA No. 70-latest edition.

C. Basic control wiring diagrams are given on pages 14 and 15.

Other control systems may be factory supplied, see User's

Information Manual and Instructions packed with control

system supplied.

D. After placing the boiler in operation, the safety shutoff device

must be tested. See page 12 safety check.

This manual is related to the following products: