Victory ii boiler sequence of operations – Slant/Fin VHS-180 User Manual

Page 23

background image

V

ICTORY

II

VHS Models

THERMOSTAT CALLS FOR HEAT

CIRCULATOR ON

IGNITION SPARK STARTS AND PILOT

VALVE OPERATOR OPENS

THERMOSTAT CALLS FOR

HEAT ENDS

CIRCULATOR OFF.

PILOT AND MAIN VALVE CLOSE.

INDUCER OFF

INDUCER (AIR BLOWER) ON

PILOT FLAME ESTABLISHED?

WAIT FOR NEXT CALL FOR HEAT

CIRCULATOR

CONTINUES TO

RUN

NATURAL GAS-S8600F

IGNITION SPARK CONTINUES.

PILOT VALVE REMAINS OPEN

UNTIL SYSTEM IS RESET.

SPARK GENERATOR OFF.

MAIN VALVE OPENS. MODULE

MONITORS PILOT FLAME

NO

NO

NO

NO

YES

YES

YES

Victory II Boiler Sequence of Operations

BOILER WATER TEMPERATURE

IS BELOW HIGH LIMIT SETTING?

AIR PROVING SWITCH

PROVED CLOSED?

23

PROPANE GAS-S8600H

IGNITION SPARK CON-

TINUES FOR APPROXI-

MATELY 90 SECONDS.

IF PILOT FLAME NOT

ESTABLISHED, SYSTEM

LOCKS OUT; SYSTEM

MUST BE MANUALLY

RESET.