positive number, or -1. 0s are shut down first, then 1s, 2s, etc. -1s are
not shut down at all. Defaults to 0
Select the Driver that will be used to communicate with the UPS.
7.
The drop down menu presents full selection of drivers from the latest
Network UPS Tools (NUT version 2.2.0) and additional information on
compatible Ups hardware can be found at http://www.networkupstools.
org/compat/stable.html
Click
8.
New Options in Driver Options if you need to set driver-specific
options for your selected NUT driver and hardware combination (more
details at http://www.networkupstools.org/doc)
Check
9.
Log Status an specify the Log Rate (minutes between
samples) if you wish the status from this UPS to be logged. These logs
can be views from the
Status: UPS Status screen
Check Enable Nagios to enable this UPS to be monitored using
10.
Nagios central management
Click Apply
11.
You can also customize the upsmon, upsd and upsc settings for this UPS
hardware directly from the command line
Configure UPS Powering the Console Server
A Monitored UPS is a UPS that the ECS0016 is drawing power through.
The purpose of configuring a Monitored UPS is in the event of a power
failure, it provides an opportunity to perform any “last gasp” actions before
power is lost. This is achieved by placing a script in /etc/config/scripts/
ups-shutdown - you may use the /etc/scripts/ups-shutdown as a template.
This script is run when then UPS reaches critical battery status.