Sierra Monitor Corporation Sentry Controller Gas Detector User Manual
Page 7

Sentry MODBUS I/O Memory Map
March 4, 2005
Page
:
6
Modbus
Address Parameter Units FIX
EGU
40060:0
Sensor 5: Sensor Disconnected
(Trouble Bits)
40060:2
Sensor 5: Voltage Regulator Failure
40060:3
Sensor 5: Sensor Bad
40060:4
Sensor 5: Duplicate Sensor
40060:5
Sensor 5: Timer Failure
40060:6
Sensor 5: Sensor Bridge Failure (Combustibles)
40060:7
Sensor 5: Type Error
40061:0
Sensor 5: Enabled
40061:1
Sensor 5: Auto Calibration Enabled
40061:2
Sensor 5: Low Alarm Latch
40061:3
Sensor 5: Calibrated
40061:4
Sensor 5: Zone Option Enabled
40061:5
Sensor 5: Calibration Table Initialized
40061:6
Sensor 5: H
2
S Sensor Resistance too high
40061:7
Sensor 5: Operate Mode (as opposed to Warm Up Mode)
40062:0
Sensor 5: High Alarm Latch
40062:1
Sensor 5: Low Sensitivity
40062:2
Sensor 5: Sensor not Valid
40064:0
Sensor 5:Concentration
% / PPM
0 - 6553.5
40070:0
Sensor 6: Sensor Disconnected
(Trouble Bits)
40070:2
Sensor 6: Voltage Regulator Failure
40070:3
Sensor 6: Sensor Bad
40070:4
Sensor 6: Duplicate Sensor
40070:5
Sensor 6: Timer Failure
40070:6
Sensor 6: Sensor Bridge Failure (Combustibles)
40070:7
Sensor 6: Type Error
40071:0
Sensor 6: Enabled
40071:1
Sensor 6: Auto Calibration Enabled
40071:2
Sensor 6: Low Alarm Latch
40071:3
Sensor 6: Calibrated
40071:4
Sensor 6: Zone Option Enabled
40071:5
Sensor 6: Calibration Table Initialized
40071:6
Sensor 6: H
2
S Sensor Resistance too high
40071:7
Sensor 6: Operate Mode (as opposed to Warm Up Mode)
40072:0
Sensor 6: High Alarm Latch
40072:1
Sensor 6: Low Sensitivity
40072:2
Sensor 6: Sensor not Valid
40074:0
Sensor 6: Concentration
% / PPM
0 - 6553.5