Sierra Monitor Corporation Sentry Controller Gas Detector User Manual
Page 16

Sentry MODBUS I/O Memory Map
March 4, 2005
Page
:
15
Modbus
Address Parameter Units FIX
EGU
40443
Sensor 8 High Conc. Time Month
40444
Sensor 8 High Conc. Time Day
40445
Sensor 8 High Conc. Time Hr
40446
Sensor 8 High Conc. Time Min
40447
Sensor 8Low Conc. Time Month
40448
Sensor 8 Low Conc. Time Day
40449
Sensor 8 Low Conc. Time Hr
40450
Sensor 8 Low Conc. Time Min
40451
Sensor 8 Trouble Time Month
40452
Sensor 8 Trouble Time Day
40453
Sensor 8 Trouble Time Hr
40454
Sensor 8 Trouble Time Min
40455
Sensor 8 Input Value - Multiplex 0
0 - 6553.5
40456
Sensor 8 Input Value - Multiplex 1
0 - 6553.5
40457
Sensor 8 Input Value - Multiplex 2
0 - 6553.5
40458
Sensor 8 Input Value - Multiplex 3
0 - 6553.5
40459
Sensor 8 Input Value - Multiplex 4
0 - 6553.5
40460
Sensor 8 Input Value - Multiplex 5
0 - 6553.5
40461
Sensor 8 Input Value - Multiplex 6
0 - 6553.5
40462
Sensor 8 Input Value - Multiplex 7
0 - 6553.5
40463
Sensor 8 Calibration Due Days
40466
Contrived alarm - Sensor 1 - 0 = no alarm, 1 = Low alarm, 2 = High alarm
40467
Contrived alarm - Sensor 2 - 0 = no alarm, 1 = Low alarm, 2 = High alarm
40468
Contrived alarm - Sensor 3 - 0 = no alarm, 1 = Low alarm, 2 = High alarm
40469
Contrived alarm - Sensor 4 - 0 = no alarm, 1 = Low alarm, 2 = High alarm
40470
Contrived alarm - Sensor 5 - 0 = no alarm, 1 = Low alarm, 2 = High alarm
40471
Contrived alarm - Sensor 6 - 0 = no alarm, 1 = Low alarm, 2 = High alarm
40472
Contrived alarm - Sensor 7 - 0 = no alarm, 1 = Low alarm, 2 = High alarm
40473
Contrived alarm - Sensor 8 - 0 = no alarm, 1 = Low alarm, 2 = High alarm