Application 2299 – Slave Mode

Siemens Building Technologies, Inc.

29

Descriptor Address

Application

Description

MA LOOPOUT

77

2283, 2286

The mixed air control loop output value that is used to
determine OA DMPR POS (Point 62).

OA LOOPOUT

77

2287

The outdoor air damper control loop output valve that is used to
determine OA DMPR POS (Point 62).

CTL TEMP

78

2281, 2283,
2284, 2286,
2287

The temperature used as input for the temperature control
loops. This value will be the same as the value in ROOM TEMP
(Point 4) unless it is overridden.

CLG LOOPOUT

79

2281, 2283,
2284, 2286,
2287

The cooling temperature control loop output value in percent.

HTG LOOPOUT

80

2281, 2283,
2284, 2286,
2287

The heating temperature control loop output value in percent.

AUX P GAIN

81

2281, 2284

The proportional gain value for the auxiliary control loop.

MA P GAIN

81

2283, 2286

The proportional gain value for the mixed air control loop.

OA P GAIN

81

2287

The proportional gain value for the outdoor air damper control
loop.

AUX l GAIN

82

2281, 2284

The integral gain value for the auxiliary control loop.

MA l GAIN

82

2283, 2286

The integral gain value for the mixed air control loop.

OA l GAIN

82

2287

The integral gain value for the outdoor air damper control loop.

AUX D GAIN

83

2281, 2284

The derivative gain value for the auxiliary control loop.

MA D GAIN

83

2283, 2286

The derivative gain value for the mixed air control loop.

OA D GAIN

83

2287

The derivative gain value for the outdoor air damper control
loop.

AUX BIAS

84

2281, 2284

The biasing of the auxiliary loopout point, AUX LOOPOUT
(Point 77).

MA BIAS

84

2283, 2286

The biasing of the mixed air loopout point, MA LOOPOUT
(Point 77).

OA BIAS

84

2287

The biasing of the outdoor air damper loopout point, OA
LOOPOUT (Point 77).

SWITCH LIMIT

85

2281, 2283,
2284, 2286,
2287

The active temperature control loop output must be less than this
value to switch between cooling mode and heating mode. Actual
switchover depends on SWITCH DBAND (Point 90) being
exceeded and is subject to SWITCH TIME (Point 86) being
expired.
Valid input: 0 to 100%

SWITCH TIME

86

2281, 2283,
2284, 2286,
2287

The time, in minutes, that must expire to switch between cooling
mode and heating mode. Actual switchover depends on the
active temperature control loop being below the value of
SWITCH LIMIT (Point 85) and exceeding the value of SWITCH
DBAND (Point 90).
Valid input: 0 to 255 minutes