Siemens 125-1957 User Manual
Page 39
Application 2299 – Slave Mode
Siemens Building Technologies, Inc.
29
Descriptor Address
Application
Description
MA LOOPOUT
77
2283, 2286
The mixed air control loop output value that is used to
determine OA DMPR POS (Point 62).
OA LOOPOUT
77
2287
The outdoor air damper control loop output valve that is used to
determine OA DMPR POS (Point 62).
CTL TEMP
78
2281, 2283,
2284, 2286,
2287
The temperature used as input for the temperature control
loops. This value will be the same as the value in ROOM TEMP
(Point 4) unless it is overridden.
CLG LOOPOUT
79
2281, 2283,
2284, 2286,
2287
The cooling temperature control loop output value in percent.
HTG LOOPOUT
80
2281, 2283,
2284, 2286,
2287
The heating temperature control loop output value in percent.
AUX P GAIN
81
2281, 2284
The proportional gain value for the auxiliary control loop.
MA P GAIN
81
2283, 2286
The proportional gain value for the mixed air control loop.
OA P GAIN
81
2287
The proportional gain value for the outdoor air damper control
loop.
AUX l GAIN
82
2281, 2284
The integral gain value for the auxiliary control loop.
MA l GAIN
82
2283, 2286
The integral gain value for the mixed air control loop.
OA l GAIN
82
2287
The integral gain value for the outdoor air damper control loop.
AUX D GAIN
83
2281, 2284
The derivative gain value for the auxiliary control loop.
MA D GAIN
83
2283, 2286
The derivative gain value for the mixed air control loop.
OA D GAIN
83
2287
The derivative gain value for the outdoor air damper control
loop.
AUX BIAS
84
2281, 2284
The biasing of the auxiliary loopout point, AUX LOOPOUT
(Point 77).
MA BIAS
84
2283, 2286
The biasing of the mixed air loopout point, MA LOOPOUT
(Point 77).
OA BIAS
84
2287
The biasing of the outdoor air damper loopout point, OA
LOOPOUT (Point 77).
SWITCH LIMIT
85
2281, 2283,
2284, 2286,
2287
The active temperature control loop output must be less than this
value to switch between cooling mode and heating mode. Actual
switchover depends on SWITCH DBAND (Point 90) being
exceeded and is subject to SWITCH TIME (Point 86) being
expired.
Valid input: 0 to 100%
SWITCH TIME
86
2281, 2283,
2284, 2286,
2287
The time, in minutes, that must expire to switch between cooling
mode and heating mode. Actual switchover depends on the
active temperature control loop being below the value of
SWITCH LIMIT (Point 85) and exceeding the value of SWITCH
DBAND (Point 90).
Valid input: 0 to 255 minutes