Siemens 125-1957 User Manual
Page 38
APOGEE Heat Pump Controller—Multi Stage Owner's Manual
28
Siemens Building Technologies, Inc.
Descriptor Address
Application
Description
CLG OUTPUT
61
2281, 2283,
2284, 2286,
2287
If the cooling control device is not DX, then the value of this
point indicates the position of the cooling actuator. If DX cooling
is used, then the value of this point determines whether DX is
ON or OFF.
Valid values: 0 to 100%
OA DMPR POS
62
2281, 2283,
2284, 2286,
2287
Indicates the position of the outdoor air damper actuator.
CLG P GAIN
63
2281, 2283,
2284, 2286,
2287
The proportional gain value for the cooling temperature control
loop.
CLG l GAIN
64
2281, 2283,
2284, 2286,
2287
The integral gain value for the cooling temperature control loop.
CLG D GAIN
65
2281, 2283,
2284, 2286,
2287
The derivative gain value for the cooling temperature control
loop.
CLG BIAS
66
2281, 2283,
2284, 2286,
2287
The biasing of the cooling temperature control loop. Refer to
CLG LOOPOUT (Point79).
HTG P GAIN
67
2281, 2283,
2284, 2286,
2287
The proportional gain value for the heating temperature control
loop.
HTG l GAIN
68
2281, 2283,
2284, 2286,
2287
The integral gain value for the heating temperature control loop.
HTG D GAIN
69
2281, 2283,
2284, 2286,
2287
The derivative gain value for the heating temperature control
loop.
HTG BIAS
70
2281, 2283,
2284, 2286,
2287
The biasing of the heating temperature control loop. Refer to
HTG LOOPOUT (Point 80).
ROOM P GAIN
71
2281, 2284
The proportional gain value for the room control loop.
ROOM I GAIN
72
2281, 2284
The integral gain value for the room control loop.
ROOM D GAIN
73
2281, 2284
The derivative gain value for the room control loop.
ROOM BIAS
74
2281, 2284
The biasing of the room loop output point, DISCH STPT (Point
93).
CMP MIN OFF
75
2284, 2286,
2287
The minimum time, in minutes, which the unit ventilator's
compressor will remain OFF before turning ON again.
Valid input: 0 to 255 minutes
CMP MlN ON
76
2284, 2286,
2287
The minimum time, in minutes, which the unit ventilator's
compressor will remain ON before turning OFF again.
Valid input: 0 - 255 minutes
AUX LOOPOUT
77
2281, 2284
The control loop output value that is used to determine AUX
OUTPUT (Point 55).