Applications

Basic Operation

The Unit Vent Controller

⎯0 to 10V Output provides Direct Digital Control (DDC) technology

for unit ventilator applications. The applications available in this controller are as follows:

Heating and/or Chilled Water Cooling,
ASHRAE Cycles l and II

Application 2281

Heating and/or Chilled Water Cooling,
ASHRAE Cycle III

Application 2283

Heating and DX Cooling,
ASHRAE Cycles I and II

Application 2284

Heating and DX Cooling,
ASHRAE Cycle III

Application 2286

Nesbitt Cycle W

Application 2287

Slave Mode (no control; available for set up,
and point extension device)

Application 2299

Control Temperature Setpoints

The controller maintains a specified temperature setpoint based on Day/Night mode, the
heating/cooling mode, or the setpoint dial (if used).

Day/Night Mode

The controller maintains the specified day setpoint temperature during daytime hours and the
specified night setpoint at night.

Day Heating Operation

The controller maintains the room temperature by resetting the unit ventilator's discharge
temperature setpoint (2281/2284), modulating the available coil control device, controlling
auxiliary radiation (if provided), positioning the outdoor air or face-bypass damper.