Application 2299 – Slave Mode

Siemens Building Technologies, Inc.

27

Descriptor Address

Application

Description

DX 44

2284,

2286,

2287

The actual status of the DX cooling compressor.

DO 5

45

2287, 2299

Digital output 5 controls a 24 Vac load with an ON or OFF
status.

EHEAT 1

45

2281, 2283,
2284, 2286

The actual status of the first stage of electric heat.

DO 6

46

2287, 2299

Digital output 6 controls a 24 Vac load with an ON or OFF
status.

EHEA T 2

46

2281, 2283,
2284, 2286

The actual status of the second stage of electric heat.

DO 7

47

2287, 2299

Digital output 7 controls a 24 Vac load with an ON or OFF
status.

EHEAT 3

47

2281, 2283,
2284, 2286

The actual status of the third stage of electric heat.

DO 8

50

2299

Digital output 8 controls a 24 Vac load with an ON or OFF
status.

FAN 50

2281,

2283,

2284, 2286,
2287

This point is a digital output used to control the fan. ON
indicates that the DO is energized; OFF indicates that the DO is
de-energized.

NGT HW HTG

53

2281, 2283,
2284, 2286,
2287

YES indicates that the heating valve will be kept open in night
mode in both heating and cooling modes (recommended for
systems with hot water). NO indicates heating valve will be
controlled normally.
Valid input: YES or NO

NGT CLG MODE

54

2281, 2283,
2284, 2286,
2287

YES indicates that night cooling is available. NO indicates that
night cooling is not available.
Valid input: YES or NO

AUX OUTPUT

55

2281, 2283,
2284, 2286

Indicates the percentage of time the auxiliary radiation will be
ON.
Valid values: 0 to 100%

AUX HTG TIME

57

2281, 2283,
2284, 2286

The period of the auxiliary radiation pulse-width modulation
algorithm.
Valid values: 0 to 255 minutes

EHT STG DELY

58

2281, 2283,
2284, 2286

Delay between a stage of electric heat changing state and the
next change of state of any stage.
Valid input: 0 to 255 seconds

DO DIR.REV

59

2281, 2283,
2284, 2286,
2287, 2299,

The configuration setup code for DOs. Allows the DOs to be
direct or reverse acting (enabled equals energized or enabled
equals de-energized).

HTG OUTPUT

60

2281, 2283,
2284, 2286,
2287

If the heating control device is a valve or face-bypass damper,
then the value of this point indicates the position of the heating
actuator. If electric heat is used, then the value of this point
determines how many stages are ON.
Valid values: 0 to 100%