This chapter presents a description of the Unit Vent Controller database including point
descriptors, point addresses, and a listing of applications in which each point is found.

Table 3. Point Database.

Descriptor Address

Application

Description

CTLR ADDRESS

01

2281, 2283,
2284, 2286,
2287, 2299

Identifies the controller on the FLN trunk.

APPLICATION 02

2281,

2283,

2284, 2286,
2287, 2299

The identification number of the program running in the
controller.
Valid entries: 2281, 2283, 2284, 2286, 2287, 2299

ROOM TEMP

04

2281, 2283,
2284, 2286,
2287, 2299

Actual reading from the room temperature sensor.

HEAT.COOL 05 2281,

2283,

2284, 2286,
2287

Current mode of operation for applications that can be either a
heating mode or a cooling mode.

DAY CLG STPT

06

2281, 2283,
2284, 2286,
2287

The temperature setpoint in degrees that the controller
maintains, during day periods in cooling mode, if a room
temperature sensor setpoint dial is not present or is not used.
Refer to STPT DIAL (Point 14).
Valid entry range: 48° to 95°F (9°- 35°C)

DAY HTG STPT

07

2281, 2283,
2284, 2286,
2287

The temperature setpoint in degrees that the controller
maintains during day periods in heating mode if a room
temperature sensor setpoint dial is not present or is not used.
Refer to STPT DIAL (Point 14).
Valid entry range: 48° to 95°F (9° to 35° C)

NGT CLG STPT

08

2281, 2283,
2284, 2286,
2287

The temperature setpoint in degrees that the controller
maintains during night periods in cooling mode.
Valid entry range: 48° to 95°F (9° to 35°C)

NGT HTG STPT

09

2281, 2283,
2284, 2286,
2287

The temperature setpoint in degrees that the controller
maintains during night periods in heating mode.
Valid entry range: 48° to 95°F (9°to 35°C)

OADPR MINPOS

10

2281, 2283,
2284, 2286,
2287

The minimum position the damper will be commanded to during
day mode.