Introduction

Siemens Building Technologies, Inc.

3

Hardware Outputs

Analog (0 to 10V)

Application

• Cooling valve actuator

2281, 2283, 2287

• Face-bypass damper actuator

2281, 2283, 2284, 2286

• Heating valve actuator

2281, 2283, 2284, 2286, 2287

• Outdoor air damper actuator

2281, 2283, 2284, 2286

Digital

Application

• Auxiliary radiation electric coil contact; or,

auxiliary radiation two-position valve actuator

2281, 2283, 2284, 2286

• Unit

fan

2281, 2283, 2284, 2286, 2287

• First stage electric heat

2281, 2283, 2284, 2286

• Second stage electric heat

2281, 2283, 2284, 2286

• Third stage electric heat

2281, 2283, 2284, 2286

• Two-position cooling valve actuator

2281, 2283, 2284, 2286

• Two-position heating valve actuator

2281, 2283, 2284, 2286

• DX

coil

2284, 2286, 2287

Power Wiring

The controller is powered by 24 Vac and connects to the two screw terminals on the
controller. Labeled “C” (Common) and “H” (Hot) on the terminal block labeled “24 VAC”. No
earth-ground connection is required (Figure 2).

Communication Wiring

The controller connects to the field panel by means of a Floor Level Network (FLN) trunk.
Communication wiring connects to the three screw terminals on the controller labeled “+”
(positive), “-“ (negative), and “S” (Shield) (Figure 3).