If the room temperature sensor input to the Unit Vent Controller fails or the LTDT equals ON,
the controller goes through the following shutdown sequence:

• Outdoor air damper is closed.

• Heating is full ON (except electric, which is OFF).

• Cooling is full OFF.

• Face-bypass damper is open to face.

• Fan is OFF.

• Auxiliary radiation is OFF.

• Two-position heating valve actuator is open.

• Two -position cooling valve actuator is closed.

NOTE:

DO 2 is not commanded by the fail-safe mode; all other DOs can be affected.

If the discharge air temperature sensor fails, the following conditions occur:

• If the last valid value is greater than 150 degrees, the heat is turned off, the outdoor

air damper is closed and the fan is turned on.

• If the sensor does not come back within 10 minutes or if the last valid value is less

than 150 degrees, the controller shuts down.

If a failed sensor returns or if the LTDT turns off, normal control resumes.

Analog and digital outputs cannot be commanded when the controller is in fail-safe mode;
however, failed points may be overridden, allowing the controller to return from fail-safe
mode. In this instance, room temperature control is not possible.