Appendices – MGE UPS Systems 250A User Manual
Page 25

34020201EN/AB
- Page 25
6. Appendices
#
Bit
R/W
NV
Description
47
R/W
NV
Major alarms on circuits 1 to 16
0
Current in circuit 01 > 80%
1
Current in circuit 02 > 80%
2
Current in circuit 03 > 80%
3
Current in circuit 04 > 80%
4
Current in circuit 05 > 80%
5
Current in circuit 06 > 80%
6
Current in circuit 07 > 80%
7
Current in circuit 08 > 80%
8
Current in circuit 09 > 80%
9
Current in circuit 10 > 80%
10
Current in circuit 11 > 80%
11
Current in circuit 12 > 80%
12
Current in circuit 13 > 80%
13
Current in circuit 14 > 80%
14
Current in circuit 15 > 80%
15
Current in circuit 16 > 80%
48
R/W
NV
Major alarms on circuits 17 to 32
0
Current in circuit 17 > 80%
1
Current in circuit 18 > 80%
2
Current in circuit 19 > 80%
3
Current in circuit 20 > 80%
4
Current in circuit 21 > 80%
5
Current in circuit 22 > 80%
6
Current in circuit 23 > 80%
7
Current in circuit 24 > 80%
8
Current in circuit 25 > 80%
9
Current in circuit 26 > 80%
10
Current in circuit 27 > 80%
11
Current in circuit 28 > 80%
12
Current in circuit 29 > 80%
13
Current in circuit 30 > 80%
14
Current in circuit 31 > 80%
15
Current in circuit 32 > 80%
49
R/W
NV
Major alarms on circuits 33 to 42
0
Current in circuit 33 > 80%
1
Current in circuit 34 > 80%
2
Current in circuit 35 > 80%
3
Current in circuit 36 > 80%
4
Current in circuit 37 > 80%
5
Current in circuit 38 > 80%
6
Current in circuit 39 > 80%
7
Current in circuit 40 > 80%
8
Current in circuit 41 > 80%
9
Current in circuit 42 > 80%
10 to 15
Unused bits (all set to 0)
50
R
NV
Reserved for MGE UPS SYSTEMS
51
R
NV
Reserved for MGE UPS SYSTEMS
52
R/W
NV
Rating of breaker on circuit 01
53
R/W
NV
Rating of breaker on circuit 02
54
R/W
NV
Rating of breaker on circuit 03
55
R/W
NV
Rating of breaker on circuit 04
56
R/W
NV
Rating of breaker on circuit 05
57
R/W
NV
Rating of breaker on circuit 06
58
R/W
NV
Rating of breaker on circuit 07
59
R/W
NV
Rating of breaker on circuit 08
60
R/W
NV
Rating of breaker on circuit 09
61
R/W
NV
Rating of breaker on circuit 10
62
R/W
NV
Rating of breaker on circuit 11
63
R/W
NV
Rating of breaker on circuit 12
64
R/W
NV
Rating of breaker on circuit 13
65
R/W
NV
Rating of breaker on circuit 14
66
R/W
NV
Rating of breaker on circuit 15
67
R/W
NV
Rating of breaker on circuit 16
68
R/W
NV
Rating of breaker on circuit 17
Circuit breaker ratings in amps (16).
Must not be modified.
These bits go to 1 when the current in a
corresponding output circuit is greater than
the major alarm threshold (80% in the
example opposite). This state is stored in
memory until the alarm is reset by setting
the bit to 0.