beautypg.com

Appendices – MGE UPS Systems 250A User Manual

Page 25

background image

34020201EN/AB

- Page 25

6. Appendices

#

Bit

R/W

NV

Description

47

R/W

NV

Major alarms on circuits 1 to 16

0

Current in circuit 01 > 80%

1

Current in circuit 02 > 80%

2

Current in circuit 03 > 80%

3

Current in circuit 04 > 80%

4

Current in circuit 05 > 80%

5

Current in circuit 06 > 80%

6

Current in circuit 07 > 80%

7

Current in circuit 08 > 80%

8

Current in circuit 09 > 80%

9

Current in circuit 10 > 80%

10

Current in circuit 11 > 80%

11

Current in circuit 12 > 80%

12

Current in circuit 13 > 80%

13

Current in circuit 14 > 80%

14

Current in circuit 15 > 80%

15

Current in circuit 16 > 80%

48

R/W

NV

Major alarms on circuits 17 to 32

0

Current in circuit 17 > 80%

1

Current in circuit 18 > 80%

2

Current in circuit 19 > 80%

3

Current in circuit 20 > 80%

4

Current in circuit 21 > 80%

5

Current in circuit 22 > 80%

6

Current in circuit 23 > 80%

7

Current in circuit 24 > 80%

8

Current in circuit 25 > 80%

9

Current in circuit 26 > 80%

10

Current in circuit 27 > 80%

11

Current in circuit 28 > 80%

12

Current in circuit 29 > 80%

13

Current in circuit 30 > 80%

14

Current in circuit 31 > 80%

15

Current in circuit 32 > 80%

49

R/W

NV

Major alarms on circuits 33 to 42

0

Current in circuit 33 > 80%

1

Current in circuit 34 > 80%

2

Current in circuit 35 > 80%

3

Current in circuit 36 > 80%

4

Current in circuit 37 > 80%

5

Current in circuit 38 > 80%

6

Current in circuit 39 > 80%

7

Current in circuit 40 > 80%

8

Current in circuit 41 > 80%

9

Current in circuit 42 > 80%

10 to 15

Unused bits (all set to 0)

50

R

NV

Reserved for MGE UPS SYSTEMS

51

R

NV

Reserved for MGE UPS SYSTEMS

52

R/W

NV

Rating of breaker on circuit 01

53

R/W

NV

Rating of breaker on circuit 02

54

R/W

NV

Rating of breaker on circuit 03

55

R/W

NV

Rating of breaker on circuit 04

56

R/W

NV

Rating of breaker on circuit 05

57

R/W

NV

Rating of breaker on circuit 06

58

R/W

NV

Rating of breaker on circuit 07

59

R/W

NV

Rating of breaker on circuit 08

60

R/W

NV

Rating of breaker on circuit 09

61

R/W

NV

Rating of breaker on circuit 10

62

R/W

NV

Rating of breaker on circuit 11

63

R/W

NV

Rating of breaker on circuit 12

64

R/W

NV

Rating of breaker on circuit 13

65

R/W

NV

Rating of breaker on circuit 14

66

R/W

NV

Rating of breaker on circuit 15

67

R/W

NV

Rating of breaker on circuit 16

68

R/W

NV

Rating of breaker on circuit 17

Circuit breaker ratings in amps (16).
Must not be modified.

These bits go to 1 when the current in a
corresponding output circuit is greater than
the major alarm threshold (80% in the
example opposite). This state is stored in
memory until the alarm is reset by setting
the bit to 0.