Installation, Module 425 mm deep – MGE UPS Systems 250A User Manual

Page 10

background image

Page 10 -

34020201EN/AB

PMM

1685,5

400 mm

1250

720 mm

2. Installation

Module 425 mm deep

2. Install the rear base panel 23 (not
mandatory).
3. Position the module.
4. Level the module using the adjustable feet

24 .

5. Attach the module to the wall using the
two rear brackets.
6. Install the base panels 23 on the sides
and front.
7. Remove the bracket 26 on the top of the
module (used only for back-to-back
assembly of two modules) and retighten the
fixing screw.

Connection cables run under the false floor
or in a trough.

Important:
At least 400 mm of free space is required
above the module to ensure correct
ventilation.
At least 720 mm of free space is required
in front to open the doors.

24

Footprint of module

Force exerted on the floor by the four feet:

28 kg/cm

2

.

Rear of module

Front of module

4 feet, diameter 40 mm

Installation against a wall

Caution: during handling, make sure the module does not fall over.

1. Turn to horizontal position the two
brackets 25 at the back used to secure the
module (see figure).

25

26

23

23

23

24

69.5

69.5

67

67

82

82

1076

276