DCa300SSC / DCa300SSCU gen. • operation anD partS manUal — rev. #1 (08/10/11) — page 35

generatOr start-Up prOceDUre (ManUaL)

6. The generator’s frequency meter (Figure 42) should be

displaying the 60 cycle output frequency in

Hertz.

Figure 42. Frequency Meter

7. The generator’s AC-voltmeter (Figure 43) will display

the generator’s output in

voltS. If the voltage is not

within the specified tolerance,

Figure 43. Voltmeter

8. Use the voltage adjustment control knob (Figure 44)

to increase or decrease the desired voltage.

Figure 44. Voltage Adjust Control Knob

9. The ammeter (Figure 45) will indicate

zero amps with

no load applied. When a load is applied, the ammeter

will indicate the amount of current that the load is

drawing from the generator.

Figure 45. Ammeter (No Load)

10. The engine oil pressure gauge (Figure 46) will indicate

the oil pressure of the engine. Under normal operating

conditions the oil pressure is approximately 28 to 85

psi. (193~586 kPa).

Figure 46. Oil Pressure Gauge

11. The

coolant temperature gauge (Figure 47) will

indicate the coolant temperature. Under normal

operating conditions the coolant temperature should

be between 167°~203°F (75°~95°C) (

green zone).

Figure 47. Coolant Temperature Gauge

12. The

tachometer gauge (Figure 48) will indicate the

speed of the engine when the generator is operating.

Under normal operating conditions this speed is

approximately 1800 RPM’s.

Figure 48. Engine Tachometer Gauge

13. Place the

main, gFCi, and aux. circuit breakers in the

on position (Figure 49).

Figure 49. Main, Aux. and GFCI

Circuit Breakers (ON)

14. Observe the generator’s ammeter (Figure 50) and

verify it reads the anticipated amount of current with

respect to the load. The ammeter will only display a

current reading if a load is in use.

Figure 50. Ammeter (Load)

15. The generator will run until manually stopped or an

abnormal condition occurs.