beautypg.com

Generator control panel – Multiquip Whisperwatt Series 60HZ Generator (Cummins QSL9-G3 Diesel Engine) DCA300SSCU User Manual

Page 18

background image

page 18 — DCa300SSC / DCa300SSCU gen. • operation anD partS manUal — rev. #1 (08/10/11)

generatOr cOntrOL paneL

Figure 4. Generator Control Panel

The definitions below describe the controls and functions

of the Generator Control Panel (Figure 4).
1.

pilot lamp — Indicates the system is running.

2.

panel light — Normally used in dark areas or at night

time. When activated, panel lights will illuminate. When

the generator is not in use be sure to turn the panel

light switch to the

oFF position.

3.

aC voltmeter — Indicates the output voltage present

at the

U,v, and W output terminal lugs.

4.

auto on/off engine Controller (mpeC) —

This controller has a vertical row of status LED’s (inset),

that when lit, indicate that an engine malfunction (fault)

has been detected. When a fault

has been detected the engine

controller will evaluate the fault

and all major faults will shutdown

the generator. During

cranking

cycle, The MPEC will attempt to

crank the engine for 10 seconds

before disengaging.

If the engine does not engage (start) by the third

attempt, the engine will be shutdown by the engine

controller’s

over Crank protection mode. If the

engine engages at a speed (RPM’s) that is not safe,

the controller will shutdown the engine by initializing

the

over Speed protection mode.

5.

main Circuit Breaker — This three-pole, 800 amp

main breaker is provided to protect the

U,v, and W

output terminal lugs from overload.

6.

voltmeter Change-over Switch — This switch allows

the AC voltmeter to indicate phase to phase voltage

between any two phases of the output terminals or to

be switched off.

7.

voltage regulator Control — Allows ±15% manual

adjustment of the generator’s output voltage.

8.

panel light Switch — When activated will turn on

control panel light.

9.

ammeter Change-over Switch — This switch allows

the AC ammeter to indicate the current flowing to the load

connected to any phase of the output terminals, or to be

switched off. This switch does not effect the generator

output in any fashion, it is for current reading only.

10.

AC Ammeter — Indicates the amount of current the

load is drawing from the generator per leg selected by

the ammeter phase-selector switch.

11.

Frequency meter — Indicates the output frequency

in hertz (Hz). Normally 60 Hz

This manual is related to the following products: