Section 4

4-6

Water Pump

WARNING

Disconnect the electric power to the ice machine at
the electric service switch box and turn off the
water supply.

1. Disconnect the water pump power cord.

Water Pump Removal

2. Disconnect the hose from the pump outlet.
3. Loosen the screws securing the pump mounting

bracket to the bulkhead.

4. Lift the pump and bracket assembly off the

screws.

Ice Thickness Probe
1. Compress the side of the ice thickness probe near

the top hinge pin and remove it from the bracket.

DISCONNECT

WIRE LEAD

SV1619

COMPRESS

HINGE PIN

TO REMOVE

ICE

THICKNESS

PROBE

Ice Thickness Probe Removal

NOTE: At this point, the ice thickness probe can
easily be cleaned. If complete removal is desired,
continue with step 2 below.

WARNING

Disconnect the electric power to the ice machine at
the electric service switch box.

2. Disconnect the wire lead from the control board

inside the electrical control box.

SV1618

PUMP

OUTLET

WATER

PUMP

POWER

CORD

LOOSEN
SCREWS