PAGE 22 — DCA-125SSJU SERIES (STANDARD) — PARTS AND OPERATION MANUAL — REV. #4 (06/03/03)

DCA-125SSJU SERIES — GENERAL INFORMATION

DCA-125SSJU Series Familiarization

Generator

The MQ Power DCA-125SSJU Series is a 100 kW

generator

(Figure 4) that is designed as a high quality portable (requires
a trailer for transport) power source for telecom sites, lighting
facilities, power tools, submersible pumps and other
industrial and construction machinery.

Engine Operating Panel

The “Engine Operating Panel” is provided with the following:
z Tachometer

z Water Temperature Gauge

z Oil Pressure Gauge

z Charging Ammeter Gauge

z Engine Throttle Handle (Up to S/N 77500507)

z Fuel Level Gauge

z Engine Speed Switch (S/N 7500508~)

z Cold Starting Button

z Panel Light

z Panel Light Switch

z Ignition/Preheat Switch ( Up to S/N 77500507)

z Auto ON/OFF Engine Controller (S/N 7500508~)
Generator Control Panel

The “Generator Control Panel” is provided with the following:
z Output Voltage Adjustment Knob

z Frequency Meter (Hz)

z AC Ammeter (Amps)

z AC Voltmeter (Volts)

z Ammeter Change-Over Switch

z Voltmeter Change-Over Switch

z Voltage Regulator

z Over-Current Relay
Output Terminal Panel

The “Output Terminal Panel” is provided with the following:
z Three 250 VAC output receptacles (CS-6369), 50 amps

z Three auxiliary circuit breakers, 250V @50 amps

z Two 125 VAC output receptacles, (GFCI), 20 amps

z Two GFCI circuit breakers, 120V@ 20amps

z Five output terminal lugs (3Ø power)
Control Box

The “Control Box” is provided with the following:
z 3-Pole, 300 amp Main Circuit Breaker

z Automatic Voltage Regulator

z Current Transformer

z Emergency Relay

Open Delta Excitation System

The DCA-125SSJU Series Generator is equipped with the state
of the art "

Open-Delta" excitation system. The open delta

system consist of an electrically independent winding wound
among stationary windings of the AC output section.

There are four connections of the open delta A, B, C and D.
During steady state loads, the power from the voltage regulator
is supplied from the parallel connections of A to B, A to D, and
C to D. These three phases of the voltage input to the voltage
regulator are then rectified and are the excitation current for the
exciter section.

When a heavy load, such as a motor starting or a short circuit
occurs, the automatic voltage regulator (AVR) switches the
configuration of the open delta to the series connection of B to
C. This has the effect of adding the voltages of each phase ot
provide higher excitation to the exciter section and thus better
voltage response during the application of heavy loads.

The connections of the AVR to the AC output windings are for
sensing only. No power is required from these windings.

The open-delta design provides virtually unlimited excitation
current, offering maximum motor starting capabilities. The
excitation does not have a "

fixed ceiling" and responds

according the demands of the required load.

Engine

The DCA-125SSJU Series Generator is powered by a
4 cycle, water cooled, turbocharged

John Deere

Model 6068TF250 Diesel engine. This engine is designed to
meet every performance requirement for the generator. Reference
Table 1 for engine specifications.

In keeping with MQ Power's policy of constantly improving its
products, the specifications quoted herein are subject to change
without prior notice.

Mechanical Governor System

The mechanical governor system control the RPM of the
engine. When the engine demands increase or decrease, the
mechanical governor system regulates the frequency varia-
tion to ±.5%. The electronic governor option increases
frequency variation to ±0.25%.

Extension Cables

When electric power is to be provided to various tools or loads
at some distance from the generator, extension cords are
normally used. Cables should be sized to allow for distance in
length and amperage so that the voltage drop between the
generator and point of use (load) is held to a minimum. Use the
cable selection chart (Table 5) as a guide for selecting proper
extension cable size.