This UPS does not include a Bypass input circuit breaker (MCCB) to
protect bypass circuit. The Bypass input circuit breaker (MCCB) is to be
field supplied and installed. Recommended Breaker (MCCB)'s
Specifications are as follows:
Capacity (kVA) Bypass Voltage (Vac) Bypass Rating (Aac)
Breaker (A)
100 480 120 150
600
96
125
150 480 180 225
600 144
200
225 480 271 350
600
217
300
300 480 361 500
600 289
400
375 480 451 600
600 361
500
500 480 601 800
600 481
600
750 480 902
1200
600 722
900
AC input and AC output overcurrent protection and disconnect devices shall be field
supplied and installed. The DC output MCCB shall be field supplied and installed. The
overcurrent protection device should be installed in the Battery cabinet and rated as
indicated in TABLE 1.4.
WARNING 2