beautypg.com

MITSUBISHI ELECTRIC 9800A SERIES UPS systems User Manual

Page 67

background image

MITSUBISHI
ELECTRIC

9800A SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

6-5

MITSUBISHI ELECTRIC 9800A SERIES UPS

UA817

EMERGENCY STOP

ACTIVATED

Emergency stop applied

-

-

Alarm

-

UA819

REMOTE START

BUTTON ABNORMAL

There is an error with the remote

start switch.

CALL SERVICE

ENGINEER

[1] Alarm -

UA820

REMOTE STOP BUTTON

ABNORMAL

There is an error with the remote

stop switch.

CALL SERVICE

ENGINEER

[1] Alarm -

UA824 CB2

OPEN

Battery disconnect circuit breaker

CB2 turned OFF

TURN ON CB2

[1]

Alarm

-

UA831

EMERGENCY BYPASS

SWITCH ON

Emergency bypass switch turned

to

- [1]

Alarm

-

UA834

BATTERY DEPLETED

INV. STOPPED

DC voltage dropped below

discharge end during inverter

operation

- -

Alarm

-

UA841

CONVERTER OPE.

PROHIBITION

Converter operation interlock

applied

- -

Alarm

-

UA842

OUTPUT CIRCUIT

ABNORMAL

Load bus voltage sensor

abnormality

- -

Alarm

-

#1: It has the possibility that output short-circuits.
#2:Check the CB3 and Bypass Thyristors.